1.3 Parameter Table
42 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u F: Options
F parameters program the drive for PG feedback from the motor and to function with option cards.
No.
(Addr.)
Name Description Setting Page
F1: PG Speed Control Card (PG-B3 / PG-X3)
Parameters F1-01, F1-05, and F1-06 include “PG 1” in the parameter name and are used to set up a PG option card plugged into option port CN5-C
of the drive.
Parameters F1-31 through F1-36 include “PG 2” in the parameter name and are used to set up a PG option card plugged into option port
CN5-B of the drive.
Other parameters in the F1 group are used to set operation for PG options plugged into ports CN5-B and CN5-C.
F1-01
(380H)
PG 1 Pulses Per
Revolution
Sets the number of PG (pulse generator or encoder) pulses.
Sets the number of pulses per motor revolution.
Default:
<10>
Min: 0 ppr
Max: 60000 ppr
163
F1-02
(381H)
Operation Selection
at PG Open Circuit
(PGo)
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
4: No alarm display
Note: Due to potential damage to motor and machinery, only
use the “Alarm only” and “No alarm display” settings
under special circumstances.
Default: 1
Min: 0
Max: 4
163
F1-03
(382H)
Operation Selection
at Overspeed (oS)
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
Default: 1
Min: 0
Max: 3
163
F1-04
(383H)
Operation Selection
at Deviation
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
Default: 3
Min: 0
Max: 3
164
F1-05
(384H)
PG 1 Rotation
Selection
0: Pulse A leads with Forward Run command
1: Pulse B leads with Forward Run command
Default:
<10>
Min: 0
Max: 1
164
F1-06
(385H)
PG 1 Division Ratio
for PG Pulse
Monitor
Sets the division ratio for the pulse monitor used for the PG option card
installed to port CN5-C.
By setting xyz as a three-digit number, the division ratio becomes = [(1 + x)
/ (y × 10 + z)].
Default: 1
Min: 1
Max: 132
164
F1-08
(387H)
Overspeed (oS)
Detection Level
Sets the overspeed detection level as a percentage of the maximum output
frequency.
Default: 115%
Min: 0%
Max: 120%
163
F1-09
(388H)
Overspeed (oS)
Detection Delay
Time
Sets the time in s for an overspeed situation to trigger a fault (oS).
Default:
<10>
Min: 0.0 s
Max: 2.0 s
163
F1-10
(389H)
Excessive Speed
Deviation (dEv)
Detection Level
Sets the excessive speed deviation (dEv) detection level as a percentage of
the maximum output frequency.
Default: 10%
Min: 0%
Max: 50%
164
F1-11
(38AH)
Excessive Speed
Deviation (dEv)
Detection Delay
Time
Sets the time in seconds for a speed deviation situation to trigger a fault
(dEv).
Default: 0.5 s
Min: 0.0 s
Max: 10.0 s
164
F1-14
(38DH)
PG Open-Circuit
Detection Time
Sets the time required to trigger a PG Open fault (PGo).
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
163
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV