1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 43
F1-20
(3B4H)
PG Option Card
Disconnect
Detection 1
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
165
F1-30
(3AAH)
PG Card Option Port
for Motor 2
Selection
Sets the port for the PG option card used by motor 2.
0: CN5-C
1: CN5-B
Default: 1
Min: 0
Max: 1
165
F1-31
(3B0H)
PG 2 Pulses Per
Revolution
Sets the number of pulses for a PG option card connected to port CN5-B.
Default:
<10>
Min: 0 ppr
Max: 60000 ppr
163
F1-32
(3B1H)
PG 2 Rotation
Selection
0: Pulse A leads with Forward Run command
1: Pulse B leads with Forward Run command
Default:
<10>
Min: 0
Max: 1
164
F1-35
(3BEH)
PG 2 Division Ratio
for Pulse Monitor
Sets the division ratio for the pulse monitor used for the PG option card 2
installed to port CN5-B.
By setting xyz as a three-digit number, the division ratio becomes = [(1 + x)
/ (y × 10 + z)].
Default: 1
Min: 1
Max: 132
164
F1-36
(3B5H)
PG Option Card
Disconnect
Detection 2
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
165
F2: Analog Input Card (AI-A3)
F2-01
(38FH)
Analog Input Option
Card Operation
Selection
0: Option card input terminals V1 and V2 replace drive analog input 1, 2,
and 3 terminals.
1: Input signals to terminals V1 and V2 are added together to create the
frequency reference.
Default: 0
Min: 0
Max: 1
165
F2-02
(368H)
Analog Input Option
Card Gain
Sets the gain for the input signal to the analog card.
Default: 100.0%
Min: -999.9%
Max: 999.9%
165
F2-03
(369H)
Analog Input Option
Card Bias
Sets the bias for the input signal to the analog card.
Default: 0.0%
Min: -999.9%
Max: 999.9%
165
F3: Contact Input Card (DI-A3)
F3-01
(390H)
Contact Input
Option Card Input
Selection
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5-digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hz or user-set units
(o1-03 = 2 or 3), the units for F3-01 are determined by o1-03.
Default: 0
Min: 0
Max: 7
166
F3-03
(3B9H)
Contact Input
Option DI-A3 Data
Length Selection
0: 8 bits
1: 12 bits
2: 16 bits
Default: 2
Min: 0
Max: 2
166