2.6 F: Option Settings
164 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Parameter F1-03 Settings:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only
Note: Due to potential damage to motor and machinery, the “Alarm only” setting should be used only under special circumstances.
n F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the frequency reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-11. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.
Settings for Parameter F1-04:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (drive continues operating while “dEv” flashes on the screen)
n F1-05, F1-32: PG 1, PG 2 Rotation Selection
Determines the direction indicated by the pulses from the PG feedback encoder for motor 1 and motor 2.
Refer to PG option card instruction manual for details on how to set the direction for the PG encoder and the motor.
Setting 0: A pulse leads with Forward run command
Setting 1: B pulse leads with Forward run command
n F1-06, F1-35: PG 1, PG 2 Division Rate for PG Pulse Monitor
Sets the division ratio for the pulse monitor used for the PG option card installed to port CN5-B or CN5-C. By setting
xyz as a three-digit number, the division ratio becomes = [(1 + x) / (y × 10 + z)]. If only using the A pulse for one track
input, then the input ratio will be 1:1, regardless of the setting of F1-06 or F1-35.
Example:
When the division ratio is 1;
F1-06 = 1, division ratio = (1 + 0)/(0 × 10 + 1) = 1
When the division ratio is 2/16 (1/8);
F1-06 = 116, division ratio = (1 + 1)/(1 × 10 + 6) = 2/16
No. Parameter Name Option Port Setting Range Default
F1-04 Operation Selection at Deviation (dEv) CN5-B, CN5-C 0 to 3 3
F1-10 Excessive Speed Deviation Detection Level CN5-B, CN5-C 0 to 50% 10%
F1-11 Excessive Speed Deviation Detection Delay Time CN5-B, CN5-C 0.0 to 10.0 s 0.5 s
No.
<1> For details on the default settings, refer to Control Mode Dependent Parameter Default Values on page 84.
Parameter Name Option Port Setting Range Default
F1-05 PG 1 Rotation Selection CN5-C 0, 1 Determined by A1-02 <1>
F1-32 PG 2 Rotation Selection CN5-B 0, 1 Determined by A1-02 <1>
No. Parameter Name Option Port Setting Range Default
F1-06 PG 1 Division Rate for PG Pulse Monitor CN5-C
1 to 132 (1 to )
1
F1-35 PG 2 Division Rate for PG Pulse Monitor CN5-B
1 to 132 (1 to )
1