156 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
2.5 E: Motor Parameters
2.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u E1: V/f Pattern for Motor 1
n E1-04 to E1-13
Figure 2. 42
Figure 2.42 V/f Pattern
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
3. When the parameters are initialized using parameter A1-03, the settings for E1-04 through E1-13 are returned to their default values.
4. Parameters E1-11, E1-12, and E1-13 should only be used to fine-tune the V/f pattern in the constant output range. These parameters
rarely need to be changed.
No. Name Setting Range Default
E1-04 Maximum Output Frequency
<1> Default setting depends on the control mode set in parameter A1-02. The value shown here is for V/f Control.
<2> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning).
<3> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<4> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<5> When vector control is used, set the no-load voltage value.
40.0 to 120.0 Hz
<1>
E1-05 Maximum Voltage 0 to 13000 V
<1> <5>
E1-06 Base Frequency 0.0 to120.0 Hz
<1>
E1-07 Middle Output Frequency 0.0 to 120.0 Hz
<1>
E1-08 Middle Output Frequency Voltage 0 to 13000 V
<1>
E1-09 Minimum Output Frequency 0.0 to 120.0 Hz
<1>
E1-10 Minimum Output Frequency Voltage 0 to 13000 V
<1>
E1-11 Middle Output Frequency 2 0.0 to 120.0 Hz 0.0 Hz <3>
E1-12 Middle Output Frequency Voltage 2 0 to 13000 V 0 V <2> <3>
E1-13 Base Voltage 0 to 13000 V 0 V <2> <4>
Output Voltage (V)
Frequency (Hz)