EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - 1.3 Parameter Table; A: Initialization Parameters

YASKAWA FSDrive-MV1000
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
1.3 Parameter Table
1.3 Parameter Table
u A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
No.
(Addr.)
Name Description Setting Page
A1: Initialization Parameters
A1-00
(100H)
<3>
Language Selection
0: English
1: Japanese
7: Chinese (Available from the drive software version S0106 and later.)
11: Polish (Available from the drive software version S0105 and later.)
<68>
Default: 1
Min: 0
Max: 11
94
A1-01
(101H)
Access Level
Selection
0: View and set A1-00, A1-01, and A1-04. U- parameters can also be
viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01
to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Min: 0
Max: 2
94
A1-02
(102H)
<3>
Control Method
Selection
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 2
Min: 0
Max: 3
95
A1-03
(103H)
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter
o2-03)
2220: 2-wire initialization (Resets all parameters to default values.)
Default: 0
Min: 0
Max: 2220
95
A1-04
(104H)
Password
When the value set in A1-04 does not match the value set in A1-04,
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-32 cannot
be changed.
Default: 0
Min: 0
Max: 9999
96
A1-06
(127H)
Application Preset
0: Disabled
Note: This function is not available. Always set this parameter
to the default value of 0 (disabled).
Default: 0 98
A1-90
(3000H)
Year Setting
Sets the year for the calendar. The setting is used for recording event log data
and trace data.
Note: Some error arises, so periodic adjustment is advisable.
Default: 2011
Min: 2000
Max: 2099
98
A1-91
(3001H)
Month and Date
Setting
Sets the month and day for the calendar. The setting is used for recording
event log data and trace data.
Note: Some error arises, so periodic adjustment is advisable.
Default: 1.01
Min: 1.01
Max: 12.31
98
A1-92
(3002H)
Hour and Minute
Setting
Sets the hour and minute for the calendar. The setting is used for recording
event log data and trace data.
Note: Some error arises, so periodic adjustment is advisable.
Default: 0.00
Min: 0.00
Max: 23.59
98
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 24 ページ 013年10月11日 金曜日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals