1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 25
A2: User Parameters
A2-01 to
A2-32
(106 to
125H)
User Parameters 1 to
32
Parameters that were recently edited are listed here. The user can also select
parameters to appear here for quicker access.
Default: 0
Min: b1-01
Max: o4-
99
A2-33
(126H)
User Parameter
Automatic Selection
0: Parameters A2-01 to A2-32 are reserved for the user to create a list of
User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters
will be saved to A2-17 through A2-32 for quicker access.
Default: 0
Min: 0
Max: 1
99
A3: Trace Data
A3-01 to
A3-32
(3010H to
302FH)
Trace Data 01 to 32
Selection
Sets the numbers of the monitor contents to be registered as the trace data. A
maximum of 32 contents can be set.
Note: 1. Set the desired monitor parameter in the digits available in
U-. For example, enter “103” for U1-03 (output
current).
2. Set 000 if the parameter is not to be used.
3. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00 or
oFC00 fault occurs, no fault trace is performed.
Default:
<10>
Min: 0
Max: 899
100
A3-33
(3030H)
High-Speed Trace
Sampling Time
Sets the sampling time for high-speed tracing in 0.001 s units. Note,
however, that if 0.000 s is set, the setting made will actually be 0.00025 s
(250 μs).
Note: 1. The maximum number of samplings for high-speed tracing is
4000 per content.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00 or
oFC00 fault occurs, no fault trace is performed.
Default: 0.000 s
Min: 0.000 s
Max: 10.000 s
100
A3-34
(3031H)
Low-Speed Trace
Sampling Time
Sets the sampling time for low-speed tracing in 0.01s units.
Note: 1. The maximum number of samplings for low-speed tracing is
500 per content.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00 or
oFC00 fault occurs, no fault trace is performed.
Default: 0.05 s
Min: 0.01 s
Max: 60.00 s
100
A3-35
(3032H)
Number of Data
after
High-Speed-Trace
Fault Detection
Sets the number of samplings of the data to be registered after a fault is
detected in high-speed tracing.
Note: 1. Available only when a fault has been detected and the drive
automatically stopped.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00 or
oFC00 fault occurs, no fault trace is performed.
Default: 200
Min: 0
Max: 250
100
A3-36
(3033H)
Number of Data
after
Low-Speed-Trace
Fault Detection
Sets the number of samplings of the data to be registered after a fault is
detected in low-speed tracing.
Note: 1. Available only when a fault has been detected and the drive
automatically stopped.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00 or
oFC00 fault occurs, no fault trace is performed.
Default: 50
Min: 0
Max: 250
100
A3-37
(3034H)
Trace Stop Selection
Selects the stop conditions for tracing.
0: Fault always detected
1: Fault detected during run
Note: When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00 or
oFC00 fault occurs, no fault trace is performed.
Default: 0
Min: 0
Max: 1
100
No.
(Addr.)
Name Description Setting Page
MV1000ParameterGuide_E_conditional.book 25 ページ 2013年10月11日 金曜日 午後8時18分