2.7 H: Terminal Functions
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 171
2.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
u H1: Contact Inputs
n H1-02 to H1-16: Functions for Contact Inputs 2 to 16
These parameters assign functions to the contact inputs. The various functions and settings are listed below in Tab le 2.21.
Table 2.20 Contact Input Parameters
Table 2.21 Contact Input Terminal Settings
No.
<1> The default setting is set to 73 and cannot be changed under the following conditions.
y The drive software version is S0108 and later.
y o2-09 is set to 2.
Name Setting Range Default
H1-02 Contact Input 2 Function Selection 1 to 9F 40: Forward Run Command (2-Wire Sequence)
H1-03 Contact Input 3 Function Selection 0 to 9F 6A: Drive Enable
H1-04 Contact Input 4 Function Selection 0 to 9F 70: Drive Enable 2
H1-05 Contact Input 5 Function Selection 0 to 9F F: Through Mode <1>
H1-06 Contact Input 6 Function Selection 0 to 9F F: Through Mode
H1-07 Contact Input 7 Function Selection 0 to 9F F: Through Mode
H1-08 Contact Input 8 Function Selection 0 to 9F F: Through Mode
H1-09 Contact Input 9 Function Selection 0 to 9F F: Through Mode
H1-10 Contact Input 10 Function Selection 0 to 9F F: Through Mode
H1-11 Contact Input 11 Function Selection 0 to 9F F: Through Mode
H1-12 Contact Input 12 Function Selection 0 to 9F F: Through Mode
H1-13 Contact Input 13 Function Selection 0 to 9F F: Through Mode
H1-14 Contact Input 14 Function Selection 0 to 9F F: Through Mode
H1-15 Contact Input 15 Function Selection 0 to 9F F: Through Mode
H1-16 Contact Input 16 Function Selection 0 to 9F F: Through Mode
Setting Function Page Setting Function Page
1 LOCAL/REMOTE Selection 172 31 PID Integral Hold 178
2 External Reference 1/2 Selection 172 32 Multi-Step Speed Reference 4 178
3 Multi-Step Speed Reference 1 172 33 Thermostatic Switch (N.C.) 178
4 Multi-Step Speed Reference 2 172 34 PID Soft Starter Cancel 178
5 Multi-Step Speed Reference 3 172 35 PID Input Level Selection 178
6 Jog Reference Selection 172 40 Forward Run Command (2-Wire Sequence) 178
7 Accel/Decel Time Selection 1 172 41 Reverse Run Command (2-Wire Sequence) 178
8 Baseblock Command (N.O.) 172 42 Run Command (2-Wire Sequence 2) 178
9 Baseblock Command (N.C.) 172 43 FWD/REV Command 2 (2-Wire Sequence 2) 178
A Accel/Decel Ramp Hold 173 44 Add Offset Frequency 1 178
B Drive Overheat Alarm (oH2) 173 45 Add Offset Frequency 2 178
C Analog Terminal Input Selection 173 46 Add Offset Frequency 3 178
E ASR Integral Reset 173 60 DC Injection Braking Command 178
F Through Mode 173 61 External Search Command 1 179
10 Up Command 173 62 External Search Command 2 179
11 Down Command 173 63 Field Weakening 179
12 Forward Jog 175 67 Communications Test Mode 179
13 Reverse Jog 175 6A Drive Enable 179
14 Fault Reset 175 70 Drive Enable 2 179
15 Fast Stop (N.O.) 175 71 Speed/Torque Control Switch 179
16 Motor 2 Selection 176 73 Door Switch NC 179
17 Fast Stop (N.C.) 175 75 Up 2 Command 179
18 Timer Function Input 176 76 Down 2 Command 179
19 PID Disable 176 77 ASR Gain Switch 180