2.4 d: Reference Settings
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 141
Select the different speed references as shown in Table 2 .1 6. Figure 2.31 illustrates the multi-step speed selection.
Table 2.16 Multi-step Speed Reference and Contact Input Combinations
Figure 2.31
Figure 2.31 Preset Reference Timing Diagram
Reference
<1> The Jog frequency overrides all other frequency references.
Multi-step
Speed
Reference 1
H1- = 3
Multi-step
Speed
Reference 2
H1- = 4
Multi-step
Speed
Reference 3
H1- = 5
Multi-step
Speed
Reference 4
H1- = 32
Jog Reference
H1- = 6
Frequency Reference 1 (set in b1-01) OFFOFFOFFOFF OFF
Frequency Reference 2 (d1-02 or analog input 1, 2) ON OFF OFF OFF OFF
Frequency Reference 3 (d1-03 or analog input 1, 2) OFF ON OFF OFF OFF
Frequency Reference 4 (d1-04) ON ON OFF OFF OFF
Frequency Reference 5 (d1-05) OFF OFF ON OFF OFF
Frequency Reference 6 (d1-06) ON OFF ON OFF OFF
Frequency Reference 7 (d1-07) OFF ON ON OFF OFF
Frequency Reference 8 (d1-08) ON ON ON OFF OFF
Frequency Reference 9 (d1-09) OFF OFF OFF ON OFF
Frequency Reference 10 (d1-10) ON OFF OFF ON OFF
Frequency Reference 11 (d1-11) OFF ON OFF ON OFF
Frequency Reference 12 (d1-12) ON ON OFF ON OFF
Frequency Reference 13 (d1-13) OFF OFF ON ON OFF
Frequency Reference 14 (d1-14) ON OFF ON ON OFF
Frequency Reference 15 (d1-15) OFF ON ON ON OFF
Frequency Reference 16 (d1-16) ON ON ON ON OFF
Jog Frequency Reference (d1-17) <1> −−−− ON
d1-02
d1-04
d1-05
d1-06
d1-07
d1-17
d1-09
d1-08
d1-14
d1-15
d1-16
d1-03
d1-01
Time
Frequency
reference
FWD (REV) Run/Stop
ON
(closed)
ON
(closed)
ON
(closed)
ON
(closed)
ON
(closed)
ON
(closed)
ON (closed) ON (closed)
ON (closed)
ON (closed)
ON (closed)
ON (closed)
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Jog Reference
Multi-step Speed Ref. 1
Multi-step Speed Ref. 4
ON (closed)
ON (closed)
(Analog
Input 1)
(Analog
Input 2)
MV1000ParameterGuide_E_conditional.book 141 ページ 2013年10月11日 金曜日 午後8時18分