2.2 b: Application
104 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
DC Injection Braking time is determined by the value set to b2-04 and by the output frequency at the time the Stop
command is input or the Run command is removed. It can be calculated by:
Figure 2. 3
Figure 2.3 DC Injection Braking Time Depending on Output Frequency
Note: If an overcurrent (OC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the
fault no longer occurs.
Setting 3: Coast to Stop with Timer
When a Stop command is input or the Run command is removed, the drive will turn off its output and the motor will
coast to a stop. The drive will not start if a Run command is input before the time t (C1-02) has expired. Cycle the Run
command that was activated during time t after t has expired to start the drive.
Figure 2. 4
Figure 2.4 Coast to Stop with Timer
The wait time t is determined by the output frequency when the Stop command is input or the Run command is removed
and by the active deceleration time.
Figure 2. 5
Figure 2.5 Run Wait Time Depending on Output Frequency
DC Injection brake time
(b2-04) × 10 × Output frequency
Max. output frequency (E1-04)
=
Output frequency when
Stop command was entered
100%
(Maximum output
frequency)
10%
DC Injection braking time
b2-0410
b2-04
Drive output shut off
Run wait time t
Run command
Output
frequency
ON ON ONOFF OFF
Min output
frequency
100%
(Max output
frequency)
Output frequency
when Stop command
was entered
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)