1.4 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 85
C5-01 ASR Proportional Gain 1 0.00 to 300.00 0.01 – – 5.00
C5-02 ASR Integral Time 1 0.000 to 10.000 0.001 s – – 5.000
C5-03 ASR Proportional Gain 2 0.00 to 300.00 0.01 – – 5.00
C5-04 ASR Integral Time 2 0.000 to 10.000 0.001 s – – 5.000
C5-06 ASR Primary Delay Time Constant 0.000 to 0.500 0.001 s – – 0.012
C5-07 ASR Gain Switching Frequency 0.0 to 120.0 0.1 – – 0.0 Hz
d3-01 Jump Frequency 1 0.0 to 120.0 0.1 0.0 Hz 0.0 Hz 0.0 Hz
d3-02 Jump Frequency 2 0.0 to 120.0 0.1 0.0 Hz 0.0 Hz 0.0 Hz
d3-03 Jump Frequency 3 0.0 to 120.0 0.1 0.0 Hz 0.0 Hz 0.0 Hz
d3-04 Jump Frequency Width 0.0 to 20.0 0.1 1.0 Hz 1.0 Hz 1.0 Hz
d5-02 Torque Reference Delay Time 0 to 1000 1 ms – – 0
E1-04 Maximum Output Frequency
40.0 to 120.0
0.1 Hz 60.0 60.0 60.0
E1-05 Maximum Voltage
0 to 13000
1 V 2000 2000 2000
E1-06 Base Frequency
0.0 to 120.0
0.1 Hz 60.0 60.0 60.0
E1-07 Middle Output Frequency
0.0 to 120.0
0.1 Hz 3.0 3.0 0.0
E1-08 Middle Output Frequency Voltage
0 to 13000
1 V 150 110 0
E1-09 Minimum Output Frequency
0.0 to 120.0
0.1 Hz 1.5 0.5 0.0
E1-10 Minimum Output Frequency Voltage
0 to 13000
1 V 90 20 0
F1-01 PG 1 Pulses Per Revolution 0 to 60000 1 ppr – – 1024
F1-05 PG 1 Rotation Selection 0 to 1 – – – 1
F1-09 Overspeed Detection Delay Time 0.0 to 2.0 0.1 s – – 0.0
F1-31 PG 2 Pulses Per Revolution 0 to 60000 1 ppr – – 1024
F1-35 PG 2 Division Ratio for Pulse Monitor 0 to 1 – – – 0.0
L1-01 Motor Overload Protection Selection 0 to 1 – 1 1 1
L4-01 Speed Agreement Detection Level 0.0 to 120.0 0.1 0.0 Hz 0.0 Hz 0.0 Hz
L4-02 Speed Agreement Detection Width 0.0 to 20.0 0.1 2.0 Hz 2.0 Hz 2.0 Hz
L4-03 Frequency Detection Level (+/-) -120.0 to 120.0 0.1 0.0 Hz 0.0 Hz 0.0 Hz
L4-04
Speed Agreement Detection Width (+/
-)
0.0 to 20.0 0.1 2.0 Hz 2.0 Hz 2.0 Hz
o1-03 Digital Operator Display Selection 0 to 3 – 0 0 0
o1-04 V/f Pattern Display Unit 0 to 1 – – – 0
<20> Range upper limit is determined by E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit.
<36> Default setting is determined by o1-03, Digital Operator Display Selection.
No. Name Setting Range Resolution
Control Modes (A1-02)
V/f (0) OLV (2) CLV (3)