2.6 F: Option Settings
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 167
n F4-03: Analog Output 5 (Terminal V1) Bias
Parameter F4-03 determines the bias. This parameter is set as a percentage of the output signal from analog output 5
(terminal V1) where 100% equals 10 V output. The terminal output voltage is limited to 10 V.
n
F4-04: Analog Output 5 (Terminal V1) Cell Selection
Parameter F4-04 determines the power cell number to be output from analog output 5 (terminal V1). This parameter is
effective when 9oo (power cell) has been set for F4-01 (Analog Output 5 (Terminal V1) Monitor Selection).
n
F4-05: Analog Output 5 (Terminal V1) Signal Level Selection
Sets the signal level for analog output 5 (terminal V1).
Setting 0: 0 to 10 Vdc
Setting 1: -10 to 10 Vdc
n F4-11: Analog Output 6 (Terminal V2) Monitor Selection
Selects the data to output from analog output 6 (terminal V2). Enter the final three digits of U- to determine which
monitor data is output from the option card. Some monitors are only available in certain control modes.
n
F4-12: Analog Output 6 (Terminal V2) Gain
Parameter F4-12 determines the gain. This parameter is set as a percentage of the output signal from analog output 6
(terminal V2) where 100% equals 10 V output. The terminal output voltage is limited to 10 V.
n
F4-13: Analog Output 6 (Terminal V2) Bias
Parameter F4-13 determines the bias. This parameter is set as a percentage of the output signal from analog output 6
(terminal V2) where 100% equals 10 V output. The terminal output voltage is limited to 10 V.
n
F4-14: Analog Output 6 (Terminal V2) Cell Selection
Parameter F4-14 determines the number of the power cell to be output from analog output 6 (terminal V2). This
parameter is effective when 9 (power cell) has been set for F4-11 (Analog Output 6 (Terminal V2) Monitor
Selection).
No. Name Setting Range Default
F4-03 Analog Output 5 (Terminal V1) Bias -999.9 to 999.9% 0.0%
No. Name Setting Range Default
F4-04 Analog Output 5 (Terminal V1) Cell Selection 1 to 15 1
No. Name Setting Range Default
F4-05 Analog Output 5 (Terminal V1) Signal Level Selection 0 or 1 1
No. Name Setting Range Default
F4-11 Analog Output 6 (Terminal V2) Monitor Selection 000 to 999 103
No. Name Setting Range Default
F4-12 Analog Output 6 (Terminal V2) Gain -999.9 to 999.9 100.0
No. Name Setting Range Default
F4-13 Analog Output 6 (terminal V2) Bias -999.9 to 999.9 0.0
No. Name Setting Range Default
F4-14 Analog Output 6 (Terminal V2) Cell Selection 1 to 15 1
MV1000ParameterGuide_E_conditional.book 167 ページ 2013年10月11日 金曜日 午後8時18分