1.5 Defaults by Drive Model Selection (o2-04)
88 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Table 1.5 3 kV Class Drives Default Settings by Drive Model Selection
L8-87
Transformer
Overheat Alarm
(TMA) Level
°C
130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130
L8-88
Transformer
Overheat Fault
(TME) Level
°C
140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140
n1-03
Hunting
Prevention Time
Constant
ms
30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
n9-02
Output Current
Detection Gain
–
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
n9-71
Input Current
Conversion
Coefficient
–
0.0235 0.0235 0.0150 0.0150 0.0150 0.0110 0.0110 0.0094 0.0094 0.0094 0.0060 0.0060 0.0060 0.0040 0.0040 0.0040 0.0030 0.0030
o2-11
Reference
Voltage for Input
Voltage Detection
V
2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
No. <61> Name Unit Default Settings
–
Model
CIMR-MV2
– 035 050 070 100 140 200 260 330 400 520 650
o2-04 Drive Model Selection – 20 21 22 23 24 25 26 27 28 29 2A
E2-11 (E4-11) Motor Rated Power kW 160 230 320 460 640 910 1190 1510 1830 2380 2970
b3-04
V/f Gain during Speed
Search
%8080808080808080808080
b3-06
Output Current 1 during
Speed Search
– 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-11
Speed Search Method
Switching Level (Speed
Estimate Type Speed
Search)
% 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
E2-01 (E4-01) Motor Rated Current A 30.0 45.0 60.0 85.0 120.0 170.0 220.0 280.0 340.0 440.0 550.0
E2-02 (E4-02) Motor Rated Slip Hz 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
E2-03 (E4-03) Motor No-Load Current A 8.0 11.0 15.0 21.0 30.0 43.0 55.0 70.0 85.0 110.0 138.0
E2-05 (E4-05)
Motor Line-to-Line
Resistance
W 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
E2-06 (E4-06)
Motor Leakage
Inductance
% 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10 (E4-10)
Motor Iron Loss for
Torque Compensation
W00000000000
L2-02
Momentary Power Loss
Ride-Thru Time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Momentary Power Loss
Ride-Thru Minimum
Baseblock Time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-04
Momentary Power Loss
Ride-Thru Voltage
Recovery Time
s 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
L2-05
Undervoltage Detection
Level (Uv)
V 940 940 940 940 940 940 940 940 940 940 940
L8-02
<62> Overheat Alarm Level – 105 105 105 105 105 105 95 105 105 100 105
No. <61> Name Unit Default Settings
–
Model
CIMR-
MV2
–
052 068 080 093 102 115 135 160 180 205 220 280 330 390 440 505 550 600
o2-04
Drive Model
Selection
–
00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11
E2-11
(E4-11)
Motor Rated
Power
kW
(HP)
170
(228)
190
(255)
260
(349)
310
(416)
340
(456)
380
(509)
450
(603)
530
(710)
600
(804)
680
(912)
730
(979)
930
(1247)
1100
(1475)
1300
(1743)
1460
(1957)
1680
(2252)
1830
(2453)
2000
(2681)