1.5 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 89
Table 1.6 4.16 kV Class Drives Default Settings by Drive Model Selection
L8-09
Output Ground Fault
Detection Selection
–11111111111
L8-33
FAN Board Use
Selection
–11111222222
L8-87
Transformer Overheat
Alarm (TMA) Level
°C 130 130 130 130 130 130 130 130 130 130 130
L8-88
Transformer Overheat
Fault (TME) Level
°C 140 140 140 140 140 140 140 140 140 140 140
n1-03
Hunting Prevention Time
Constant
ms 30 30 30 30 30 30 30 30 30 30 30
n9-02
Output Current
Detection Gain
– 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
n9-71
Input Current
Conversion Coefficient
– 0.0340 0.0340 0.0235 0.0150 0.0110 0.0094 0.0060 0.0060 0.0040 0.0040 0.0030
o2-11
Reference Voltage for
Input Voltage Detection
V 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
No. <61> Name Unit Default Settings
–
Model
CIMR-
MV2
–
039 052 058 064 077 093 102 115 125 155 190 220 250 285 315 340 375 440 505 575 625
o2-04
Drive Model
Selection
–
54 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53
E2-11
(E4-11)
Motor Rated
Power
kW
(HP)
300
(402)
300
(402)
330
(442)
370
(496)
440
(590)
540
(724)
590
(791)
660
(885)
720
(965)
890
(1193)
1100
(1475)
1270
(1702)
1440
(1931)
1640
(2198)
1820
(2440)
1960
(2627)
2160
(2895)
2540
(3405)
2910
(3901)
3310
(4436)
3600
(4826)
b3-04
V/f Gain
during Speed
Search
%
80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
b3-06
Output Current
1 during Speed
Search
–
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-11
Speed Search
Method
Switching
Level (Speed
Estimate Type
Speed Search)
%
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
E2-01
(E4-01)
Motor Rated
Current
A
40.0 40.0 50.0 50.0 70.0 80.0 90.0
100.0 110.0 130.0 160.0 190.0
210.0
240.0 270.0 290.0 320.0 370.0 430.0 490.0 530.0
E2-02
(E4-02)
Motor Rated
Slip
Hz
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
E2-03
(E4-03)
Motor
No-Load
Current
A
10.0 10.0 13.0 13.0 18.0 20.0 23.0 25.0 28.0 33.0 40.0 48.0 53.0 60.0 68.0 73.0 80.0 93.0
108.0 123.0 133.0
E2-05
(E4-05)
Motor
Line-to-Line
Resistance
W
0.300
0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
0.300
0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
E2-06
(E4-06)
Motor Leakage
Inductance
%
20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10
(E4-10)
Motor Iron
Loss for
Torque
Compensation
W
0 00000000 0 0 0 0 0 0 0 0 0 0 0 0
No. <61> Name Unit Default Settings
–
Model
CIMR-MV2
– 035 050 070 100 140 200 260 330 400 520 650
o2-04 Drive Model Selection – 20 21 22 23 24 25 26 27 28 29 2A
E2-11 (E4-11) Motor Rated Power kW 160 230 320 460 640 910 1190 1510 1830 2380 2970