1.5  Defaults by Drive Model Selection (o2-04)
90  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
L2-02
Momentary 
Power Loss 
Ride-Thru 
Time
s
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Momentary 
Power Loss 
Ride-Thru 
Minimum 
Baseblock 
Time
s
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-04
Momentary 
Power Loss 
Ride-Thru 
Vo l t a g e  
Recovery Time
s
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
L2-05
Undervoltage 
Detection 
Level (Uv)
V
1188 1188 1188 1188 1188 1188 1188 1188 1188  1188  1188  1188  1188 1188  1188  1188  1188  1188  1188  1188  1188 
L8-02
<62>
Overheat 
Alarm Level 
–
105 105 105 105 105 105 105 105 105 105 105 95 95 105 105 105 105 100 100 105 105
L8-09
Output Ground 
Fault Detection 
Selection
–
1 11111111 1 1 1 1 1 1 1 1 1 1 1 1
L8-33
FAN Board 
Use Selection
–
1 11111111 2 2 2 2 2 2 2 2 2 2 2 2
L8-87
Transformer 
Overheat 
Alarm (TMA) 
Level
°C
130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130
L8-88
Transformer 
Overheat Fault 
(TME) Level
°C
140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140
n1-03
Hunting 
Prevention 
Time Constant
ms
30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
n9-02
Output Current 
Detection Gain
–
1.0000
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
n9-71
Input Current 
Conversion 
Coefficient
–
0.0235
0.0235 0.0235 0.0235 0.0150 0.0150 0.0150 0.0110 0.0110
0.0094 0.0094 0.0060 0.0060 0.0060 0.0060 0.0040 0.0040 0.0040 0.0040 0.0030 0.0030
o2-11
Reference 
Voltage for 
Input Voltage 
Detection
V
4160
4160 4160 4160 4160 4160 4160 4160 4160
4160 4160 4160 4160 4160 4160 4160 4160 4160 4160 4160 4160
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive. 
No. <61> Name Unit Default Settings
–
Model 
CIMR-
MV2
–
039 052 058 064 077 093 102 115 125 155 190 220 250 285 315 340 375 440 505 575 625
o2-04
Drive Model 
Selection
–
54 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53
E2-11 
(E4-11)
Motor Rated 
Power
kW
(HP)
300
(402)
300
(402)
330
(442)
370
(496)
440
(590)
540
(724)
590
(791)
660
(885)
720
(965)
890
(1193)
1100
(1475)
1270
(1702)
1440
(1931)
1640
(2198)
1820
(2440)
1960
(2627)
2160
(2895)
2540
(3405)
2910
(3901)
3310
(4436)
3600
(4826)