1.3 Parameter Table
62 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
H4-23
(3066H)
Analog Output 3
Bias
Sets the amount of bias added to the voltage output via analog output 3.
Default: 0.0%
Min: -999.9%
Max: 999.9%
198
H4-24
(3067H)
Analog Output 3
Cell Selection
Sets the number of the Power Cell to be output from analog output 3. This
setting is effective when 9 (Power Cell) has been set for H4-21 (Analog
Output 3 Monitor Selection).
Default: 1
Min: 0
Max: 15
198
H4-25
(3068H)
Analog Output 3
Signal Level
Selection
Sets the signal level for analog output 3.
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
200
H4-31
(306EH)
Analog Output 4
Monitor Selection
Sets the monitor signal for output from analog output 4. Set this parameter to
the last three digits (-) of the desired U- parameter. Some U
parameters are available only in certain control modes.
Default: 000
Min: 000
Max: 999
198
H4-32
(306FH)
Analog Output 4
Gain
Sets the gain for voltage output via analog output 4.
Default: 100.0%
Min: -999.9%
Max: 999.9%
198
H4-33
(3070H)
Analog Output 4
Bias
Sets the amount of bias added to the voltage output via analog output 4.
Default: 0.0%
Min: -999.9%
Max: 999.9%
198
H4-34
(3071H)
Analog Output 4
Cell Selection
Sets the number of the Power Cell to be output from analog output 3. This
setting is effective when 9 (Power Cell) has been set for H4-31 (Analog
Output 4 Monitor Selection).
Default: 1
Min: 0
Max: 15
198
H4-35
(3072H)
Analog Output 4
Signal Level
Selection
Sets the signal level for analog output 4.
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
200
H5: MEMOBUS/Modbus
Seri
al Communication
H5-01
(425H)
<32>
Drive Node Address
Selects drive station node number (address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle power for the setting to take effect.
Default: 1F
Min: 0
Max: FFH
<38>
H5-02
(426H)
Communication
Speed Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Default: 3
Min: 0
Max: 8
<38>
H5-03
(427H)
Communication
Parity Selection
0: No parity
1: Even parity
2: Odd parity
Default: 0
Min: 0
Max: 2
<38>
H5-04
(428H)
Stopping Method
After
Communication
Error (CE)
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
Default: 3
Min: 0
Max: 3
<38>
No.
(Addr.)
Name Description Setting Page
MV1000ParameterGuide_E_conditional.book 62 ページ 2013年10月11日 金曜日 午後8時18分