n H4-04, H4-14, H4-24, H4-34: Analog Output 1, 2, 3, 4 Cell Selection
Parameters H4-04, H4-14, H4-24, and H4-34 set the power cell numbers to be output from analog outputs 1 to 4. Their
settings are effective when 9 (power cell) has been set for H4-01, H4-11, H4-21 and H4-31 (Analog Output 1 to 4
Monitor Selections).
Figure 2.69
Figure 2.69 Analog Output Gain and Bias Setting
No. Name Setting Range Default
H4-04
<1> The following table shows the power cell numbers to be output from analog outputs 1 to 4 depending on the settings.
Analog Output 1 Cell Selection 1 to 15 <1> 1
H4-14 Analog Output 2 Cell Selection 1 to 15 <1> 1
H4-24 Analog Output 3 Cell Selection 1 to 15 <1> 1
H4-34 Analog Output 4 Cell Selection 1 to 15 <1> 1
Setting 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Power cell No. A1 B1 C1 A2 B2 C2 A3 B3 C3 A4 B4 C4 A5 B5 C5
Output Voltage
Output Voltage
0 V
5 V
10 V
Gain 150%
Bias 0%
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Monitor Value
0%
H4-05, 15, 25, 35 = 0 H4-05, 15, 25, 35 = 1
10V
-10 V
100%
5 V
15V
-5 V
-15 V
-100%
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
Gain 100%
Bias 30%
Gain 100%
Bias 0%
Monitor V
alue
Monitor Value
0 V
3 V
10 V
100%0%
Output Voltage
Output V
oltage
H4-05, 15, 25, 35 = 0 H4-05, 15, 25, 35 = 1
10V
-10 V
100%
5 V
15 V
-5 V
-15 V
-100%