2.2  b: Application
122  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
n b5-12: 1PID Feedback Loss Detection Selection
Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
Setting 0: Contact output only
A contact output set for “PID feedback low” (H2- = 3E) will be triggered if the PID feedback value is below the 
detection level set to b5-13 for the time set to b5-14 or longer. A contact output set for “PID feedback high” (H2- = 
3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to 
b5-37. Neither a fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output 
resets when the feedback value leaves the loss detection range.
Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback 
Low” alarm will be displayed and a contact output set for “PID feedback low” (H2- = 3E) will be triggered. If the 
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm 
will be displayed and a contact output set for “PID feedback high” (H2- = 3F) will be triggered. Both events trigger 
an alarm output (H1- = 10). The drive will continue operation. The alarm and outputs reset when the feedback value 
leaves the loss detection range.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set in b5-14, a “FbL - Feedback Low” 
fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set in b5-37, a 
“FbH - Feedback High” fault will be displayed. Both events trigger a fault output (H2- = E) and cause the drive to 
stop the motor.
Setting 3: Contact output only, even if PID is disabled by contact input
Same as b5-12 = 0. Detection remains active when PID is disabled by a contact input (H1- = 19).
Setting 4: Feedback loss alarm, even if PID is disabled by contact input
Same as b5-12 = 1. Detection remains active when PID is disabled by a contact input (H1- = 19).
Setting 5: Feedback loss fault, even if PID is disabled by contact input
Same as b5-12 = 2. Detection remains active when PID is disabled by a contact input (H1- = 19).
n
b5-13: PID Feedback Low Detection Level
Sets the feedback level used for PID feedback low detection. The PID feedback must fall below this level for longer than 
the time b5-14 before feedback loss is detected.
n
b5-14: PID Feedback Low Detection Time
Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.
n
b5-36: PID Feedback High Detection Level
Sets the feedback level used for PID feedback high detection. The PID feedback must exceed this level for longer than 
the time b5-37 before feedback loss is detected.
No. Name Setting Range Default
b5-12 PID Feedback Loss Detection Selection 0 to 5 0
No. Name Setting Range Default
b5-13 PID Feedback Loss Detection Level 0 to 100% 0%
No. Name Setting Range Default
b5-14 PID Feedback Loss Detection Time 0.0 to 25.5 s 1.0 s
No. Name Setting Range Default
b5-36 PID Feedback High Detection Level 0 to 100% 100%