2.9  n: Special Adjustments
228  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
• If the Synchronous Transfer command input is active, the following detections will be disabled: momentary power loss 
ride-thru, fault restart function, phase loss detection, and ground fault detection.
n
n7-51: Synchronous Transfer Mode
Selects if the Synchronous Transfer is enabled.
Setting 0: Disabled
The Synchronous Transfer will not operate.
Setting 1: Enabled
Use this setting if the Synchronous Transfer is used.
Before this setting is enabled, assign the Synchronous Transfer to the multi-function contact inputs and multi-function 
contact outputs. If there are any assignment errors with the multi-function contacts, an operation error (OPE20) will 
occur.
n
n7-52: Amplitude Synchronous P Gain
Sets the proportional gain of the control that synchronizes the amplitudes of the commercial power supply voltage and 
the drive output voltage.
If Synchronous Transfer control is in effect and the drive output voltage oscillates, decrease the setting.
n
n7-53: Amplitude Synchronous I Time
Sets the integral time of the control that synchronizes the amplitudes of the commercial power supply voltage and the 
drive output voltage.
If Synchronous Transfer control is in effect and the drive output voltage oscillates, increase the setting.
n
n7-54: Amplitude Synchronous Primary Delay Time Constant
Sets the primary delay filter of the control that synchronizes the amplitudes of the commercial power supply voltage and 
the drive output voltage.
If Synchronous Transfer control is in effect and the drive output voltage oscillates, increase the setting.
n
n7-55: Amplitude Synchronous Output Limit
Sets the output limit of the control that synchronizes the amplitudes of the commercial power supply voltage and the 
drive output voltage. Set as a percentage of the voltage class.
No. Name Setting Range Default
n7-51 Synchronous Transfer Mode 0, 1 0
No. Name Setting Range Default
n7-52 Amplitude Synchronous P Gain 0.000 to 1.000 0.040
No. Name Setting Range Default
n7-53 Amplitude Synchronous I Time 0 to 1000 ms 20 ms
No. Name Setting Range Default
n7-54 Amplitude Synchronous Primary Delay Time Constant 0.000 to 1.000 s 0.200 s
No. Name Setting Range Default
n7-55 Amplitude Synchronous Output Limit 0 to 20% 10%