1.3  Parameter Table
36  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
d1-11
(28CH)
Frequency 
Reference 11
Sets the frequency reference for the drive. Setting units are determined by 
parameter o1-03.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d1-12
(28DH)
Frequency 
Reference 12
Sets the frequency reference for the drive. Setting units are determined by 
parameter o1-03.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d1-13
(28EH)
Frequency 
Reference 13
Sets the frequency reference for the drive. Setting units are determined by 
parameter o1-03.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d1-14
(28FH)
Frequency 
Reference 14
Sets the frequency reference for the drive. Setting units are determined by 
parameter o1-03.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d1-15
(290H)
Frequency 
Reference 15
Sets the frequency reference for the drive. Setting units are determined by 
parameter o1-03.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d1-16
(291H)
Frequency 
Reference 16
Sets the frequency reference for the drive. Setting units are determined 
according to the frequency reference selection/display unit setting (o1-03).
Default: 0.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d1-17
(292H)
Jog Frequency 
Reference
Sets the Jog frequency reference. Setting units are determined by parameter 
o1-03.
Default: 6.00 Hz
Min: 0.00 Hz
Max: 120.00 Hz 
<20>
140
d2: Frequency Upper/Lower Limits
d2-01
(289H)
Frequency 
Reference Upper 
Limit
Sets the frequency reference upper limit as a percentage of the maximum 
output frequency.
Default: 100.0%
Min: 0.0%
Max: 110.0%
142
d2-02
(28AH)
Frequency 
Reference Lower 
Limit
Sets the frequency reference lower limit as a percentage of the maximum 
output frequency.
Default: 0.0%
Min: 0.0%
Max: 110.0%
142
d2-03
(293H)
Master Speed 
Reference Lower 
Limit
Sets the lower limit for frequency references from analog inputs as a 
percentage of the maximum output frequency.
Default: 0.0%
Min: 0.0
Max: 110.0%
142
d3: Jump Frequency
d3-01
(294H)
Jump Frequency 1
Eliminates problems with resonant vibration of the motor/machine by 
avoiding continuous operation in predefined frequency ranges. The drive 
accelerates and decelerates the motor through the prohibited frequency 
ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz 
<20>
143
d3-02
(295H)
Jump Frequency 2 143
d3-03
(296H)
Jump Frequency 3 143
d3-04
(297H)
Jump Frequency 
Width
Sets the dead-band width around each selected prohibited frequency 
reference point.
Default: 1.0 Hz
Min: 0.0 Hz
Max: 20.0 Hz
143
d4: Frequency Reference Hold and Up/Down 2 Function
d4-01
(298H)
Frequency 
Reference Hold 
Function Selection
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency 
that was saved.
Default: 0
Min: 0
Max: 1
144
d4-03
(2AAH)
Frequency 
Reference Bias Step 
(Up/Down 2)
Sets the bias added to the frequency reference when the Up 2 and Down 2 
contact inputs are enabled (H1- = 75, 76). 
Default: 0.00 Hz
Min: 0.00 Hz
Max: 99.99 Hz
146
No.
(Addr.)
Name Description Setting  Page
MV1000ParameterGuide_E_conditional.book  36 ページ  2013年10月11日 金曜日 午後8時18分