1.3  Parameter Table
38  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
d5-06
(29FH)
Speed/Torque 
Control Switchover 
Time
Sets the delay time for switching between Speed and Torque Control using 
an input terminal (H1- = 71). 
Within the time set for the speed/torque control switching timer, analog 
inputs (torque reference, speed limit values) are held at their value at the 
moment of the “speed/torque control switching” change. Complete the 
preparations for switching externally during this period.
Default: 0 ms
Min: 0 ms
Max: 1000 ms
153
d5-08
(2B5H)
Unidirectional 
Speed Limit Bias
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
153
d6: Field Weakening and Field Forcing
d6-01
(2A0H)
Field Weakening 
Level
Sets the drive output voltage for the Field Weakening function as a 
percentage of the maximum output voltage.
Enabled when a contact input is set for Field Weakening (H1- = 63).
Default: 80%
Min: 0%
Max: 100%
154
d6-02
(2A1H)
Field Weakening 
Frequency Limit
Sets the lower limit of the frequency range where Field Weakening control is 
valid.
The Field Weakening command is valid only at frequencies above this 
setting and only when the output frequency matches the frequency reference 
(speed agree).
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
154
d6-03
(2A2H)
Field Forcing 
Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
154
d6-06
(2A5H)
Field Forcing Limit
Sets the upper limit of the excitation current command during magnetic field 
forcing. A setting of 100% is equal to motor no-load current. Disabled only 
during DC Injection Braking.
Default: 200%
Min: 100%
Max: 400%
154
d7: Offset Frequency
d7-01
(2B2H)
Offset Frequency 1
Added to the frequency reference when the contact input “Offset Frequency 
1” (H1- = 44) is switched on. Set as a percentage of the maximum 
output frequency.
Default: 0.0%
Min: -100.0%
Max: 100.0%
155
d7-02
(2B3H)
Offset Frequency 2
Added to the frequency reference when the contact input “Offset Frequency 
2” (H1- = 45) is 
switched on. Set as a percentage of the maximum 
output frequency.
Default: 0.0%
Min: -100.0%
Max: 100.0%
155
d7-03
(2B4H)
Offset Frequency 3
Added to the frequency reference when the contact input “Offset Frequency 
3” (H1- = 46) is switched on. Set as a percentage of the maximum 
output frequency.
Default: 0.0%
Min: -100.0%
Max: 100%
155
<10> Default setting is determined by A1-02, Control Method Selection.
<20> Range upper limit is determined by d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
No.
(Addr.)
Name Description Setting  Page
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV