EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - Page 40

YASKAWA FSDrive-MV1000
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.3 Parameter Table
40 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
E2-08
(315H)
Motor Iron-Core
Saturation
Coefficient 2
Sets the motor iron saturation coefficient at 75% of magnetic flux.
Automatically set during Auto-Tuning.
Default: 0.75
Min: E2-07
Max: 0.75
158
E2-09
(316H)
Motor Mechanical
Loss
Sets the motor mechanical loss as a percentage of motor rated power (W).
Adjust the setting in the following circumstances:
When there is a large amount of torque loss due to motor bearing friction
When there is a large amount of torque loss in a fan or pump application
Default: 0.0%
Min: 0.0%
Max: 10.0%
158
E2-10
(317H)
Motor Iron Loss for
Torque
Compensation
Sets the motor iron loss.
Default:
<6>
Min: 0 W
Max: 65535 W
158
E2-11
(318H)
Motor Rated Power
Sets the motor rated capacity in kW (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Default:
<6>
Min: 0 kW
Max: 65000 kW
159
E3: V/f Pattern for Motor 2
E3-01
(319H)
Motor 2 Control
Mode Selection
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 2
Min: 0
Max: 3
160
E3-04
(31AH)
Motor 2 Maximum
Output Frequency
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In
this case, the setting for E3-08 will be disregarded. Ensure that the four
frequencies are set according to these rules or an oPE10 fault will occur:
E3-04 E3-06 > E3-07 E3-09
Note: E3-07 and E3-08 are only available in the following
control modes: V/f Control, Open Loop Vector.
Default: <25>
Min: 40.0 Hz
Max: 120.0 Hz
160
E3-05
(31BH)
Motor 2 Maximum
Vo l t a g e
Default:
<25>
Min: 0.0 V
Max: 13000 V
160
E3-06
(31CH)
Motor 2 Base
Frequency
Default:
<25>
Min: 0 Hz
Max: 120 Hz
160
E3-07
(31DH)
Motor 2 Mid Output
Frequency
Default:
<25>
Min: 0.0 Hz
Max: 120.0 Hz
160
E3-08
(31EH)
Motor 2 Mid Output
Frequency Voltage
Default:
<25>
Min: 0 V
Max: 13000 V
160
E3-09
(31FH)
Motor 2 Minimum
Output Frequency
Default:
<25>
Min: 0.0 Hz
Max: 120.0 Hz
160
E3-10
(320H)
Motor 2 Minimum
Output Voltage
Default:
<25>
Min: 0 V
Max: 13000 V
160
E3-11
(345H)
<24>
Motor 2 Mid Output
Frequency 2
Default: 0.0
Min: 0.0 Hz
Max: 120.0 Hz
160
E3-12
(346H)
<24>
Motor 2 Mid Output
Frequency Voltage 2
Default: 0 V
Max: 0 V
Max: 13000 V
160
E3-13
(347H)
Motor 2 Base
Vo l t a g e
Default: 0 V
<69>
Max: 0 V
Max: 13000 V
160
E4: Motor 2 Parameters
E4-01
(321H)
Motor 2 Rated
Current
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Default:
<6>
Min: 10% of drive
rated current
Max: 200% of
drive rated current
161
E4-02
(322H)
Motor 2 Rated Slip
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Default:
<6>
Min: 0.00 Hz
Max: 20.00 Hz
161
No.
(Addr.)
Name Description Setting Page
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
Output Voltage (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09 E3-07 E3-06 E3-11 E3-04
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 40 ページ 013年10月11日 金曜日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000