1.3  Parameter Table
48  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
F7-13
(3F1)
Address Mode at 
Startup
Selects how the option address is set.
0: Static
<48>
1: BOOTP
2: DHCP
Default: 2
Min: 0
Max: 2
–
F7-14
(3F2)
Duplex Mode 
Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default: 1
Min: 0
Max: 2
–
F7-15
(3F3)
<50>
Communication 
Speed Selection
Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
Default: 10
Min: 10
Max: 100
–
F7-16
(3F4)
Communication 
Loss Time-out
Sets the time-out value for communication loss detection in tenths of a 
second. A value of 0 disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min: 0
Max: 300
–
F7-17
(3F5)
EtherNet/IP Speed 
Scaling Factor
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH 
Object.
Default: 0
Min: -15
Max: 15
–
F7-18
(3F6)
EtherNet/IP Current 
Scaling Factor
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID 
2AH Object.
Default: 0
Min: -15
Max: 15
–
F7-19
(3F7)
EtherNet/IP Torque 
Scaling Factor
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH 
Object.
Default: 0
Min: -15
Max: 15
–
F7-20
(3F8)
EtherNet/IP Power 
Scaling Factor
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH 
Object.
Default: 0
Min: -15
Max: 15
–
F7-21
(3F9)
EtherNet/IP Voltage 
Scaling Factor
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH 
Object.
Default: 0
Min: -15
Max: 15
–
F7-22
(3FA)
EtherNet/IP Time 
Scaling
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH 
Object.
Default: 0
Min: -15
Max: 15
–
F7-23 to 
F7-32
(3FB to 
404)
Dynamic Output 
Assembly 
Parameters
Parameters used in Output Assembly 116. Each parameter contains a 
MEMOBUS/Modbus address. The value received for Output Assembly 116 
will be written to this corresponding MEMOBUS/Modbus address. A 
MEMOBUS/Modbus address value of 0 means that the value received for 
Output Assembly 116 will not be written to any 
MEMOBUS/Modbus 
register.
Default: 0 –
F7-33 to 
F7-42
(405 to 
40E)
Dy
namic Input 
Assembly 
Parameters
Parameters used in Input Assembly 166. Each parameter contains a 
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will 
be read from this corresponding MEMOBUS/Modbus address. A 
MEMOBUS/Modbus address value of 0 means that the value sent for Input 
Assembly 166 is not defined by the user, therefore the option default register 
value will be returned. 
Refer to EtherNet/IP Technical Manual for definitions of the default 
MEMOBUS/Modbus registers.
Default: 0 –
<3> Parameter setting value is not reset to the default value when the drive is initialized (A1-03 = 1110/2220).
<10> Default setting is determined by A1-02, Control Method Selection.
<47> Cycle power for setting changes to take effect.
<48> If F7-13 is set to 0, then all IP Addresses (as defined with parameters F7-01 to F7-04) must be unique.
<49> Set F7-01 to F7-12 when F7-13 is set to 0.
<50> Set F7-15 when F7-14 is set to 0 or 2.
No.
(Addr.)
Name Description Setting  Page
MV1000ParameterGuide_E_conditional.book  48 ページ  2013年10月11日 金曜日 午後8時18分