1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 77
U1-12
(4BH)
Drive Status
Verifies the drive operation status.
No signal output
available
––
U1-13
(4EH)
Analog Input 1
Input Voltage
Displays the voltage of analog input 1.
10 V: 100% 0.1% –
U1-14
(4FH)
Analog Input 2
Input Voltage
Displays the input voltage of analog input 2.
10 V: 100% 0.1% –
U1-16
(53H)
Output
Frequency after
Soft Starter
Displays output frequency with ramp time and S-curves. Units determined
by o1-03.
10 V: Max
frequency
0.01 Hz –
U1-17
(58H)
DI-A3 Input
Status
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital card input
selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bits
No signal output
available
––
U1-18
(61H)
oPE Fault
Parameter
Displays the parameter number that caused the oPE or Err (EEPROM
write error) error.
No signal output
available
––
U1-19
(66H)
MEMOBUS/
Modbus Error
Code
Displays the contents of a MEMOBUS/Modbus error.
No signal output
available
––
U1-21
(77H)
AI-A3 Terminal
V1 Input Voltage
Monitor
Displays the input voltage to terminal V1 on analog input card AI-A3.
10 V: 100% 0.1% –
U1-22
(72AH)
AI-A3 Terminal
V2 Input Voltage
Monitor
Displays the input voltage to terminal V2 on analog input card AI-A3.
10 V: 100% 0.1% –
U1-23
(72BH)
AI-A3 Terminal
V3 Input Voltage
Monitor
Displays the input voltage to terminal V3 on analog input card AI-A3.
10 V: 100% 0.1% –
U1-25
(4DH)
Software
Number (Flash)
Displays FLASH ID.
No signal output
available
––
U1-26
(5BH)
Software No.
(ROM)
Displays ROM ID.
No signal output
available
––
No.
(Addr.)
Name Description
Analog Output
Level
Unit Page
All Modes
U1
-
12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
During ready
During alarm detection
During fault detection
1: ON 0: OFF
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
CRC Error
Data Length Error
Not used
(always OFF)
Parity Error
Overrun Error
Framing error
Time Out
Not used
(always OFF)
1: ON 0: OFF
U1
-
19=
00000000
All Modes
All Modes
All Modes
All Modes
All Modes