5.4 Fault Detection
128 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Digital Operator Display Fault Name
SEr
Too Many Speed Search Restarts
The number of Speed Search restarts exceeded the number set to b3-19.
Cause Possible Solution
Speed Search parameters are set to the wrong
values.
Reduce the detection compensation gain during Speed Search (b3-10).
Increase the current level when attempting Speed Search (b3-17).
Increase the detection time during Speed Search (b3-18).
Repeat Auto-Tuning.
Digital Operator Display Fault Name
TME
Transformer Temperature Fault
The temperature of the transformer has increased and has exceeded the protection level set
to L8-87.
Cause Possible Solution
Cooling fan fault If the cooling airflow is inadequate, replace the cooling fan.
The intake filter is soiled. If the intake filter is soiled, clean it.
Parameter setting error Check the parameter settings.
Thermistor fault and disconnected signal line
If the problem occurs even at a low temperature, for example immediately after
switching on the power, contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
TME1
Transformer Temperature Fault 1
The temperature of the transformer has increased and has exceeded the temperature fault
level.
Cause Possible Solution
Cooling fan fault If the cooling airflow is inadequate, replace the cooling fan.
The intake filter is soiled. If the intake filter is soiled, clean it.
Parameter setting error Check the parameter settings.
Thermistor fault and disconnected signal line
If the problem occurs even at a low temperature, for example immediately after
switching on the power, contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
TME2
Transformer Temperature DI Fault
A fault was detected from a contact input terminal (transformer overheat) on the control
board.
Cause Possible Solution
Cooling fan fault If the cooling airflow is inadequate, replace the cooling fan.
The intake filter is soiled. If the intake filter is soiled, clean it.
Overheated transformer and disconnected
signal line
If the problem occurs even at a low temperature, for example immediately after turning
the power on, contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
UL3
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer
than the allowable time (L6-03).
Cause Possible Solution
Parameter settings are not appropriate for the
load.
Check the settings of parameters L6-02 and L6-03.
Fault on the machine side.
Example: If there is undertorque, the pulley
belt may be broken.
Check the status of the machine.
Remove the cause of the fault.
Digital Operator Display Fault Name
UL4
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer
than the allowable time (L6-06).
Cause Possible Solution
Parameter settings are not appropriate for the
load.
Check the settings of parameters L6-05 and L6-06.
Fault on the machine side.
Example: If there is undertorque, the pulley
belt may be broken.
Check the load for any problems.
Remove the cause of the fault.