7.2 Options
180 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
◆ Panel Housed Type
Table 7.2 Options
◆ Separate Installation Type
Table 7.3 Options
PG Speed
Controller Card <2>
Complementary Type
PG Interface
PG-B3
For control modes requiring a PG encoder for motor feedback.
• Phase A, B, and Z pulse (3-phase) inputs (complementary type)
• Max. input frequency: 50 kHz
• Pulse monitor output: Open collector, +24 V, max. current 30 mA
• Power supply output for PG: +12 V, max. current 200 mA
Complementary Type PG
Installation Manual
(TOBPC73060036)
Line Driver PG
Interface
PG-X3
For control modes requiring a PG encoder for motor feedback.
• Phase A, B, and Z pulse (differential pulse) inputs (RS-422)
• Max. input frequency: 300 kHz
• Pulse monitor output: RS-422
• Power supply output for PG: +5 V or +12 V, max. current 200 mA
Motor PG Feedback
Line Driver Interface
Installation Manual
(TOBPC73060037)
PLC Function
Expansion PLC Board
BC-620
Supplements PLC functions required to customize the drive.
• Program memory capacity: Equivalent to 8,000 steps
• Execution speed: 1,000 steps/1 ms
• Language: Ladder language, textual language
<3>
<1> Only one optional communication card can be selected.
<2> To apply PG control, the PG speed control card must be selected.
<3> Documentation is being prepared.
Type Name Function Reference Manual
Momentary
Power Loss
Compensation
<1> Under development
<2> Documentation is being prepared.
Uninterruptible Power
Supply (UPS) Unit
UPS is installed inside the panel and backs up a control power supply
when momentary power losses occur.
This option is required to implement measures against momentary
power loss (for the speed search function or KEB function)
–
Continuation of
Operation
Backup Cooling Fan
<1>
Automatically enables continued operation of the drive in case of one
of the cooling fans fails to operate. (N + 1 backup system)
<2>
Measures for Cold
Regions
Space Heater
Suppresses dew condensation inside the panel by adding a space
heater circuit.
Note: This option does not always prevent dew
condensation. Use the drive in an environment
with no dew condensation.
–
Panel Door Open Interlock
Detects opening of the panel door by adding a limit switch.
Medium-voltage power shutdown command is output on detecting
opening.
–
Type Name Function Reference Manual
Maintenance
<1> Under development
<2> Documentation is being prepared.
USB Copy Unit
JVOP-181
Enables the copying and transfer of parameters between drives
using (one-touch) simple operations. This unit can also be used as
a conversion connector between the communication port (RJ-45)
of an drive and a USB port of a PC running DriveWizard Plus MV.
This option comprises a copy unit with USB interface, an RJ-45
cable and a USB cable.
<2>
Power Cell
Replacement
Lifter for Replacing
Power Cells
Facilitates power cell replacement.
Note: A maintenance space of at least 2000 mm must
be secured in front of the panel in order to
replace Power Cells with a lifter.
Refer to Periodic
Inspection &
Maintenance on page 159.
Installation
Inrush Current
Suppression
Circuit
<1>
Suppresses the inrush current on turning the drive power on by
adding a circuit (inrush suppression circuit panel)
<2>
Type Name Function Reference Manual