7.2 Options
180 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Panel Housed Type
Table 7.2 Options
Separate Installation Type
Table 7.3 Options
PG Speed
Controller Card <2>
Complementary Type
PG Interface
PG-B3
For control modes requiring a PG encoder for motor feedback.
Phase A, B, and Z pulse (3-phase) inputs (complementary type)
Max. input frequency: 50 kHz
Pulse monitor output: Open collector, +24 V, max. current 30 mA
Power supply output for PG: +12 V, max. current 200 mA
Complementary Type PG
Installation Manual
(TOBPC73060036)
Line Driver PG
Interface
PG-X3
For control modes requiring a PG encoder for motor feedback.
Phase A, B, and Z pulse (differential pulse) inputs (RS-422)
Max. input frequency: 300 kHz
Pulse monitor output: RS-422
Power supply output for PG: +5 V or +12 V, max. current 200 mA
Motor PG Feedback
Line Driver Interface
Installation Manual
(TOBPC73060037)
PLC Function
Expansion PLC Board
BC-620
Supplements PLC functions required to customize the drive.
Program memory capacity: Equivalent to 8,000 steps
Execution speed: 1,000 steps/1 ms
Language: Ladder language, textual language
<3>
<1> Only one optional communication card can be selected.
<2> To apply PG control, the PG speed control card must be selected.
<3> Documentation is being prepared.
Type Name Function Reference Manual
Momentary
Power Loss
Compensation
<1> Under development
<2> Documentation is being prepared.
Uninterruptible Power
Supply (UPS) Unit
UPS is installed inside the panel and backs up a control power supply
when momentary power losses occur.
This option is required to implement measures against momentary
power loss (for the speed search function or KEB function)
Continuation of
Operation
Backup Cooling Fan
<1>
Automatically enables continued operation of the drive in case of one
of the cooling fans fails to operate. (N + 1 backup system)
<2>
Measures for Cold
Regions
Space Heater
Suppresses dew condensation inside the panel by adding a space
heater circuit.
Note: This option does not always prevent dew
condensation. Use the drive in an environment
with no dew condensation.
Panel Door Open Interlock
Detects opening of the panel door by adding a limit switch.
Medium-voltage power shutdown command is output on detecting
opening.
Type Name Function Reference Manual
Maintenance
<1> Under development
<2> Documentation is being prepared.
USB Copy Unit
JVOP-181
Enables the copying and transfer of parameters between drives
using (one-touch) simple operations. This unit can also be used as
a conversion connector between the communication port (RJ-45)
of an drive and a USB port of a PC running DriveWizard Plus MV.
This option comprises a copy unit with USB interface, an RJ-45
cable and a USB cable.
<2>
Power Cell
Replacement
Lifter for Replacing
Power Cells
Facilitates power cell replacement.
Note: A maintenance space of at least 2000 mm must
be secured in front of the panel in order to
replace Power Cells with a lifter.
Refer to Periodic
Inspection &
Maintenance on page 159.
Installation
Inrush Current
Suppression
Circuit
<1>
Suppresses the inrush current on turning the drive power on by
adding a circuit (inrush suppression circuit panel)
<2>
Type Name Function Reference Manual

Table of Contents