EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - Insufficient Starting Torque; Motor Rotates after the Drive Output Is Shut off (Motor Rotates During DC Injection Braking); Output Frequency Is Not as High as Frequency Reference; Motor Does Not Restart after Power Loss

YASKAWA FSDrive-MV1000
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.11 Troubleshooting without Fault Display
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions 157
Troubleshooting
5
Insufficient Starting Torque
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection
Braking)
Output Frequency is not as High as Frequency Reference
Motor Does Not Restart after Power Loss
Reverse drive output frequency and speed detection.
When output frequency rises, the sensor detects a
speed decrease.
Set PID output for reverse characteristics (b5-09 = 1).
Adjustment made to PID parameter settings are
insufficient.
Make the adjustments by referring to the information on the PID control
parameters (b5-) in the separate FSDrive-MV1000 Parameter Guide.
Cause Possible Solutions
Auto-Tuning has not yet been performed (required for
vector control modes).
Perform Auto-Tuning. Refer to Motor Performance Fine-Tuning on page 110.
The control mode was changed after performing
Auto-Tuning.
Perform Auto-Tuning again.
Only Stationary Auto-Tuning was performed. Perform Rotational Auto-Tuning.
Cause Possible Solutions
DC Injection Braking is set too low and the drive
cannot decelerate properly.
Adjust the DC Injection braking settings.
Increase the current level for DC Injection Braking (b2-02).
Increase the DC Injection Braking time at stop (b2-04).
The stopping method is set so that the drive coasts to
stop.
Set b1-03 (Stopping Method Selection) to 0 or 2.
Cause Possible Solutions
Frequency reference is set within the range of the
Jump frequency.
Adjust the parameters used for the Jump frequency function (d3-01, d3-02, d3-
03, d3-04).
Note: Enabling the Jump frequency prevents the drive from outputting
the frequencies specified in the Jump range.
Upper limit for the frequency reference has been
exceeded.
Set the maximum output frequency and the upper limit for the frequency
reference to more appropriate values (E1-04, d2-01).
Note: The following calculation yields the upper value for the output
frequency = E1-04 x d2-01 / 100
Large load triggered Stall Prevention function during
acceleration.
Reduce the load.
Adjust the Stall Prevention level during acceleration (L3-02).
Cause Possible Solutions
The Run command was not issued again when power
was restored.
Check the sequence and wiring that has been set up to enter the Run command.
A relay should be set up to make sure the Run command remains enabled
throughout any power loss.
Cause Possible Solutions

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals