3.2 Standard Connection Diagram
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions 57
3.2 Standard Connection Diagram
The standard connection diagram for the drive is shown below. For the operating method, see Start-Up Programming &
Operation on page 77.
NOTICE: Consider voltage tolerance levels and insulation in applications with a high input voltage or particularly long wiring distances.
Contact your Yaskawa representative or the nearest Yaskawa sales office.
◆ Class: 2 kV
Figure 3.1
Figure 3.1 Drive Standard Connection Diagram (Example: CIMR-MV2A6AA052)
Main circuit power supply,
AC 3-phase
2.4 kV
60 Hz
Ground resistance:
less than 10 Ω
Control power supply,
AC single-phase
200/220 V
50/60 Hz
RC
SC
Input voltage Input current
Output
voltage
Frequency reference
4 to 20 mA DC
Cooling fan power supply
Controller power supply
M
Output frequency
4 to 20 mA DC
Output current
4 to 20 mA DC
Analog output: 4 points
-10 V to +10 V
Phase-A/B/Z input
RS-232
CN4-1
215IF
or
218IF
(Ethernet)
Analog input: 2 points
-10 V to +10 V
Digital input: 8 points
CN21, 22CN4-2
CN14-1
AO_1
GND
FG
1
2
3
AO_2
GND
FG
1
2
3
CN13-1
AI_1
GND
FG
CN13-2
1
2
3
Expansion PLC
board (option)
Current detection
resistance board
ISO
AMP
ISO
AMP
ISO
AMP
L4
L6
L5
L7
L8
L9
L1
L3
L2
Main circuit input
terminals
Main circuit output
terminals
Grounding of the
main circuit
terminal EA
Control power supply
terminals
Analog input terminals
Analog output
terminals
1
2
3
R
S
T
R
S
T
R
S
U
W
V
CN14-2
Ground resistance:
less than 100 Ω
Grounding of the
control system
terminal ED
CN10-1
RS-232
CN10-2
USB
USB
RS-485
CN10-3
MC ON
CN9
MC ANS
Terminals for inrush current
suppression circuit (option)
DI
DO
CN14-3
1
2
3
1
2
3
CN14-4
Digital output: 8 points
(Option)
Digital output: 8 points
Digital input: 8 points
CN12-2
CN11-2
Complementary PG
board (option)
I/O or communication
board (option)
(Option)
(Option)
(Option)
Phase-A/B/Z input
Line driver PG board
(option)
Digital operator
RJ-45
DriveWizard Plus MV
RJ-45
RS-232
To panel board
From expansion PLC board
Panel board
200/220 Vac
Sequence input
terminals
Sequence output
terminals
Medium-voltage
primary panel on
Operation interlock
13
4
3
14
1
2
15
Stop
command
Run
command
Relay circuit
Reserved
External fault
reset
Reserved
CN11-1
6
5
8
7
10
9
Major fault
During run
Drive ready
Minor fault
Medium-voltage
power shutdown
command
E
E
CN12-1
30
31
32
42
41
33
34
35
36
37
38
39
40
Relay board
I/O
Relay circuit
Complementary
output PG
Line driver
output PG
PG
L19
L20
L21
L22
L23
L24
L25
Phase-A signal
Phase-B signal
Ground
PG
L19
L20
L21
L22
L23
L24
L25
Phase-A signal
Phase-B signal
Ground
12 V or 5.5 V ±5%,
max. 200 mA
12 V or 5.5 V ±5%,
max. 200 mA
Either one or two boards can be
installed by setting parameter.
Output
(transfer
contact)
26
27
28
L48
L47
ISO
AMP
ISO
AMP
Relay circuit
Relay
board
(option)
USB copy unit (option)