4.6 Auto-Tuning
96 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
◆ Auto-Tuning Operation Example
The operation procedure based on the example of the Rotational Auto-Tuning is described below. Check that the “A1-
02” setting (Control Mode Selection) is set to “3” (Closed Loop Vector Control).
■
Selecting the Type of Auto-Tuning
■ Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Operating Procedure LCD Display
1 Turn on the power to the drive. The initial display appears.
2
Press the or key until the Auto-Tuning display appears.
3
Press to begin setting parameters.
4
Press to select the value for T1-01.
<1>
<1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1- =
16).
5
Save the setting by pressing .
6 The display automatically returns to the display shown in Step 3.
Operating Procedure LCD Display
1
Press to access the motor output power parameter T1-02.
2
Press to display the value set in “E2-11” (Motor Rated Power) at power
on.
3
Press , , , and to enter the motor power
nameplate data in kW.
4
Press to save the setting.
5 The display automatically returns to the display in Step 1.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.0A
DRV
FREF(OPR)
Rdy
JOG FWD FWD/REV
LSEQ
LREF
HELP
- MODE - PRG
Auto-Tuning
DATA
AUTO
FWD
- A.TUNE -
T1-01= 0
∗0∗
Standard Tuning
PRG
Tuning Mode Sel
ESC FWD DATA
- A.TUNE -
T1-01= 0
∗0∗
Standard Tuning
PRG
Tuning Mode Sel
FWD
“0”
- A.TUNE -
T1-01= 0
∗0∗
Standard Tuning
PRG
Tuning Mode Sel
ESC FWD DATA
- A.TUNE -
T1-02= 20000kW
(0 ~ 65000)
PRG
Mtr Rated Power
ESC FWD DATA
“20000kW”
- A.TUNE -
T1-02= 20000kW
(0 ~ 65000)
PRG
Mtr Rated Power
FWD
“20000kW”
F1
- A.TUNE -
T1-02= 25000kW
(0 ~ 65000)
PRG
Mtr Rated Power
FWD
“25000kW”
Entry Accepted
- A.TUNE -
T1-02= 25000kW
(0 ~ 65000)
PRG
Mtr Rated Power
ESC FWD DATA
“25000kW”