94 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
4.6 Auto-Tuning
4.6 Auto-Tuning
◆ Auto-Tuning Type
Select the optimal Auto-Tuning based on the conditions such as your application, control mode of the drive, and
installation environment of the motor. When selecting the Auto-Tuning to run, refer to the flowcharts shown in Start-Up
Flowcharts on page 90.
Note: The Auto-Tuning parameters valid for the control mode set for A1-02 are shown.
■ Auto-Tuning for Induction Motors
This feature sets the following parameters for induction motors automatically.
• Motor parameters E1- and E2- (E3-, E4- for motor 2)
•F1- parameters for speed feedback detection (only when Closed Loop Vector Control is set)
Table 4.6 Types of Auto-Tuning for Induction Motors
Set the data indicated in Table 4.7 before starting Auto-Tuning.
The information required for setting can be found on the motor nameplate or in the motor test report. For details on the
procedure for Auto-Tuning, refer to Subchart A-1: Simple Motor Setup Using V/f Control, or Serial Operation of
Multiple Motors on page 91 or Subchart A-2: High Performance Operation Using OLV or CLV on page 92.
Table 4.7 Input Data for Auto-Tuning for Induction Motors
Type
Parameter
Setting
Application Condition and Benefit
Control Mode to Be
Applied
Rotational Auto-Tuning T1-01 = 0
• The motor can turn around during the Auto-Tuning:
This allows the most precise control of the motor.
• Running with constant output
Open Loop Vector Control
Closed Loop Vector Control
Stationary Auto-Tuning
for Line-to-Line
Resistance
T1-01 = 2
• Tunes the drive after the cable between the drive and
motor has been replaced with a cable over 50 m long.
Assumes Auto-Tuning has already been performed.
• Drive and motor capacities differ.
V/f Control
Open Loop Vector Control
Closed Loop Vector Control
Input Data
<1> Set this when Closed Loop Vector control is selected.
Parameter Units
Auto-Tuning Type (T1-01)
Rotational Auto-Tuning (0)
Auto-Tuning for
Line-to-Line Resistance (2)
Motor Rated Power T1-02 kW Yes Yes
Motor Rated Voltage T1-03 V Yes No
Motor Rated Current T1-04 A Yes Yes
Motor Base Frequency T1-05 Hz Yes No
Number of Motor Pole T1-06 – Yes No
Motor Base Speed T1-07
min
-1
Yes No
PG Number of Pulses Per
Revolution
T1-08 – <1> No
Motor No-Load Current T1-09 A No No
Motor Rated Slip T1-10 Hz No No
Motor Iron Loss T1-11 W No No