2.2 Mechanical Installation
42 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
NOTICE: When bolting frames to each other, make secure connections by using the tightening torque indicated in this manual. Any
space between two frames may cause a leakage of cooling air, resulting in drive failure.
Installation
Accuracy of Drive
Panels
Use a measuring instrument such as a theodolite to measure the levelness on the installation base at 1-meter
intervals, and adjust to achieve a levelness error of within ±2 mm.