Parameter Details
5
5.2 b: Application
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 207
Figure 5.21 Example of How the Timer Function Works with H2-01 Terminals
Note:
When the terminal is triggered, it continues for a minimum of 100 ms. The on/off-delay time of MFDO terminal does not have an effect.
â–  b4-01: Timer Function ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-01
(01A3)
Timer Function ON-Delay
Time
Sets the ON-delay time for the timer input. 0.0 s
(0.0 - 3000.0 s)
â–  b4-02: Timer Function OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-02
(01A4)
Timer Function OFF-Delay
Time
Sets the OFF-delay time for the timer input. 0.0 s
(0.0 - 3000.0 s)
â–  b4-03: Terminal M1-M2 ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-03
(0B30)
Expert
Terminal M1-M2 ON-Delay
Time
Sets the delay time to activate the contact after the function set in H2-01 activates. 0 ms
(0 - 65000 ms)
â–  b4-04: Terminal M1-M2 OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-04
(0B31)
Expert
Terminal M1-M2 OFF-Delay
Time
Sets the delay time to deactivate the contact after the function set in H2-01 deactivates. 0 ms
(0 - 65000 ms)
â–  b4-05: Terminal M3-M4 ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-05
(0B32)
Expert
Terminal M3-M4 ON-Delay
Time
Sets the delay time to activate the contact after the function set in H2-02 activates. 0 ms
(0 - 65000 ms)
â–  b4-06: Terminal M3-M4 OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-06
(0B33)
Expert
Terminal M3-M4 OFF-Delay
Time
Sets the delay time to deactivate the contact after the function set in H2-02 deactivates. 0 ms
(0 - 65000 ms)

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control