EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
5
5.2 b: Application
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 187
5.2 b: Application
b parameters set these functions:
Frequency reference source/Run command source
Stopping method settings
DC Injection Braking
Speed Search
Timer Function
PID control
Energy Savings Control
b1: Operation Mode Selection
b1 parameters set the operation mode for the drive.
b1-01: Frequency Reference Selection 1
No.
(Hex.)
Name Description
Default
(Range)
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference. 1
(0 - 3)
Note:
Push on the keypad to set the input mode to HAND and enter the frequency reference from the keypad.
When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Minimum Output Frequency] value,
on the keypad will flash. Examine the setting for the frequency reference input and enter a value E1-09.
0 : Keypad
The bypass uses the keypad to enter the frequency reference and also switches the PID setpoint to YA-01 [Setpoint 1].
Use and on the keypad to change the frequency reference.
1 : Analog Input
The bypass uses MFAI on the bypass board to input an analog frequency reference with a voltage or current input
signal.
Voltage Input
Refer to Table 5.18 to use a voltage signal input to one of the MFAI terminals.
Table 5.18 Frequency Reference Voltage Input
Terminal Terminal Signal Level
Parameter Settings
Note
Signal Level Selection Gain Bias
Bypass MFAI 0 - 10 V Z2-30 = 0 Z2-32 Z2-33 Set Jumper Switch S2 to V for
voltage input.
Figure 5.1 Example of Setting the Frequency Reference with a Voltage Signal to the Bypass MFAI

Table of Contents

Other manuals for YASKAWA HV600

Related product manuals