9.19 Defaults by Bypass and Drive Model
688 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
9.19 Defaults by Bypass and Drive Model
The values for parameter o2-04 change the default settings for the parameters in these tables:
â—† 208/240 V
No. Name Unit Default
-
Bypass
Model
-
D002
D003
D004
D007
D010
A002
A003
A004
A006
A009
D016
A015
D024
A022
D030
A028
D046
A042
D059
A054
D074
A068
D088
A080
o2-04
Drive
Model
(KVA)
Selection
Hex. 65 67 68 6A 6B 6D 6E 6F
E2-11
Motor
Rated
Power
HP
(kW)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current
Level 1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b3-11
Spd Est
Method
Switch-over
Level
% 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
b3-12
Speed Search
Current
Deadband
- 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
b3-26
Direction
Determina
tion Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-04
Energy
Saving
Coefficient
Value
- 156.8 122.9 94.75 72.69 70.44 63.13 57.87 51.79
C6-02
Carrier
Frequency
Selection
- 2 2 2 2 2 2 2 2
E2-01
Motor Rated
Current
(FLA)
A 10.6 16.7 24.2 30.8 46.2 59.4 74.8 88
E2-02
Motor Rated
Slip
Hz 2.90 2.73 1.50 1.30 1.70 1.60 1.67 1.70
E2-03
Motor No-
Load Current
A 3.00 4.50 5.10 8.00 11.2 15.2 15.7 18.5
E2-05
Motor Line-
to-Line
Resistance
Ω 1.601 0.771 0.399 0.288 0.230 0.138 0.101 0.079
E2-06
Motor
Leakage
Inductance
% 18.4 19.6 18.2 15.5 19.5 17.2 20.1 19.5
E2-10
Motor Iron
Loss
W 77 112 172 262 245 272 505 538
L2-02
Power Loss
Ride
Through
Time
s 0.7 0.9 1.5 1.8 2.0 2.0 2.0 2.0
L2-03
Minimum
Baseblock
Time
s 0.5 0.6 0.7 0.8 0.9 1 1 1

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control