5.7 H: Terminal Functions
264 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■ H1-73: Terminal S3 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-73
(39ED)
RUN
Terminal S3 Off-Delay Time Sets the length of time necessary for Terminal S3 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
■ H1-74: Terminal S4 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-74
(39EE)
RUN
Terminal S4 Off-Delay Time Sets the length of time necessary for Terminal S4 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
■ H1-75: Terminal S5 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-75
(39EF)
RUN
Terminal S5 Off-Delay Time Sets the length of time necessary for Terminal S5 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
■ H1-76: Terminal S6 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-76
(39F0)
RUN
Terminal S6 Off-Delay Time Sets the length of time necessary for Terminal S6 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
■ H1-77: Terminal S7 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-77
(39F1)
RUN
Terminal S7 Off-Delay Time Sets the length of time necessary for Terminal S7 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
◆ MFDI Setting Value
Selects a function set with H1-01 to H1-07.
■ 3: Multi-Step Speed Reference 1
Setting Value Function Description
3 Multi-Step Speed Reference
1
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
Note:
Refer to “Setting Procedures for Multi-step Speed Operation” in “d: Reference Settings” for more information.
■ 4: Multi-Step Speed Reference 2
Setting Value Function Description
4 Multi-Step Speed Reference
2
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
Note:
Refer to “Setting Procedures for Multi-step Speed Operation” in “d: Reference Settings” for more information.