Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 263
â–  H1-63: Terminal S3 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-63
(39E3)
RUN
Terminal S3 On-Delay Time Sets the length of time necessary for Terminal S3 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
â–  H1-64: Terminal S4 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-64
(39E4)
RUN
Terminal S4 On-Delay Time Sets the length of time necessary for Terminal S4 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
â–  H1-65: Terminal S5 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-65
(39E5)
RUN
Terminal S5 On-Delay Time Sets the length of time necessary for Terminal S5 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
â–  H1-66: Terminal S6 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-66
(39E6)
RUN
Terminal S6 On-Delay Time Sets the length of time necessary for Terminal S6 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
â–  H1-67: Terminal S7 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-67
(39E7)
RUN
Terminal S7 On-Delay Time Sets the length of time necessary for Terminal S7 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
â–  H1-71: Terminal S1 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-71
(39EB)
RUN
Terminal S1 Off-Delay Time Sets the length of time necessary for Terminal S1 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
â–  H1-72: Terminal S2 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H1-72
(39EC)
RUN
Terminal S2 Off-Delay Time Sets the length of time necessary for Terminal S2 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control