Parameter List
9
9.18 U: Monitors
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 687
No.
(Hex.)
Name Description MFAO Signal Level
UC-09
(3DB8)
MSTP L MAC Found Shows the lowest MAC address found on the network. This will report the lowest value MAC
address to which the token was passed by any node on the MSTP loop.
Unit: Hex
No signal output available
UC-10
(3DB9)
MSTP # Nodes Found Shows the number of unique nodes that transmitted a token on the local MSTP loop.
Unit: 1
No signal output available
UC-11
(3DBA)
# of BN COV Sbscrpt Shows the number of COV subscriptions requested by the nodes on the BACnet network. This is
limited to the number of objects that support COV subscriptions.
Unit: 1
No Signal output available
UC-12
(3DBB)
MSTP Loop TIme Shows the number of milliseconds between drive transmitted token and drive token received,
showing how long the MSTP loop took to pass the token to all nodes on the MSTP network.
Unit: 1 ms
No signal output available
UC-13
(3DBC)
Expert
BN MSTP CRC Errors Shows the number of CRC errors detected after you energize the drive.
Unit: 1
No signal output available
UC-14
(3DBD)
Expert
BN MSTP Tokens Lost Shows the number of token losses seen by the unit since power-on. This is sensed by a net deadtime
of more than 500 ms.
Unit: 1
No signal output available
UC-15
(3DBE)
Expert
BN MSTP Tokens Retry Shows the number of token retries seen by the unit since power-on. This is sensed by two subsequent
token frames seen from the same node to the same node with the same CRC.
Unit: 1
No signal output available
UC-16
(3DBF)
Expert
BN MSTP Silence Avg Shows the average net deadtime (space between active messages), averaged over a 60 packet period.
Unit: 1.0 ms
No signal output available

Table of Contents