9.18 U: Monitors
686 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name Description MFAO Signal Level
Ub-15
(878E)
Previous Fault MMDD Displays the month and day of the previous fault.
Unit: -
No signal output available
Ub-16
(878F)
Previous Fault HHMM Displays the hour and minute of the previous fault.
Unit: -
No signal output available
Ub-17
(8790)
Contactor Voltage Displays the measured voltage for the power going to the contactor coils.
Unit: 1 Vac
No signal output available
Ub-18
(8791)
Software Version Displays the software version currently programmed into the bypass.
Unit: -
No signal output available
Ub-19
(8792)
Date Year YYYY Displays the current year.
Unit: -
No signal output available
Ub-20
(8793)
Date Month Day MMDD Displays the current date (Month and Date).
Unit: -
No signal output available
Ub-21
(8794)
Time Hour Min HHMM Displays the current time (Hours and Minutes).
Unit: -
No signal output available
Ub-22
(8795)
Bypass Analog Input Bypass MFAI level
Unit: 0-100%
No signal output available
Ub-23
(8796)
Motor 1 Overload Motor 1 Overload level
Unit: 0-100%
No signal output available
Ub-24
(8797)
Motor 2 Overload Motor 2 Overload level
Unit: 0-100%
No signal output available
Ub-94
(87DD)
Bypass CPU Usage Current Bypass CPU Load
Unit: 0-100%
No signal output available
Ub-95
(87DE)
Line Frequency Calculated AC line frequency
Unit: Hz
No signal output available
Ub-96
(87DF)
Byp Phase Loss Level Current Phase Loss level
Unit: 0-100%
No signal output available
Ub-99
(87E2)
Expert
Desired HV600 software
version
Shows the latest version of HV600 software that this version of HV600 Bypass software supports.
Unit: -
No signal output available
UC: BACnet Diagnostic Monitors
No.
(Hex.)
Name Description MFAO Signal Level
UC-01
(3DB0)
BN MSTP Net Health Shows a number between 0.0% and 100.0% that identifies the health of the MSTP network. This
number is dependent on the number of CRC errors, token losses, token retries, and net deadtime
perceived.
Unit: 0.1%
No signal output available
UC-02
(3DB1)
BACnet Tokens Rx Shows the number of received MSTP Tokens after you energize the drive.
Unit: 1
No signal output available
UC-03
(3DB2)
BACnet Tokens Tx Shows the number of transmitted MSTP Tokens after you energize the drive.
Unit: 1
No signal output available
UC-04
(3DB3)
BACnet Messages Rx Shows the number of messages with data (non-token, non-polling) received by the drive.
Unit: 1
No signal output available
UC-05
(3DB4)
BACnet Messages Tx Shows the number of messages with data (non-token, non-polling) transmitted by the drive.
Unit: 1
No signal output available
UC-06
(3DB5)
MSTP Next Node Addr Shows the next known node in the MSTP loop. This is the node to which the drive will pass the
token.
Unit: Hex
No signal output available
UC-07
(3DB6)
MSTP Prev Node Addr Shows the previous known node in the MSTP loop. This is the node from which the drive received
the token.
Unit: Hex
No signal output available
UC-08
(3DB7)
MSTP H MAC Found Shows the highest MAC address found on the network. This will report the highest value MAC
address to which the token was passed by any node on the MSTP loop.
Unit: Hex
No signal output available