• Current Input
Refer to Table 5.19 to use a current signal input to one of the MFAI terminals.
Table 5.19 Frequency Reference Current Input
Terminal Signal Level
Parameter Settings
Note
Signal Level Selection Gain Bias
Bypass MFAI 4 - 20 mA Z2-30 = 2 Z2-32 Z2-33 Set Jumper Switch S2 to “I” for current
input.
0 - 20 mA Z2-30 = 3
Figure 5.2 Example of Setting the Frequency Reference with a Current Signal to the Bypass MFAI
Changing between Master and Auxiliary Frequency References
2 : Serial Communications
The bypass uses serial communications to enter the frequency reference.
3 : Option PCB
The bypass uses a communications option card or input option card connected to the bypass control board to enter the
Run command.
Note:
If b1-01 = 3, but you did not connect a communications option card, oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the keypad.
■ b1-02: Run Command Selection 1
No.
(Hex.)
Name Description
Default
(Range)
b1-02
(0181)
Run Command Selection 1 Sets the input method for the Run command. 7
(0 - 9)
0 : Keypad
The bypass uses the keypad to enter the Run command.
Note:
The on the keypad is on while keypad is the Run command source.
1 : Digital Input
The bypass uses the control circuit terminals to enter the Run command. Select the input method for the Run
command with an Z2-xx parameter.
Set Z2-xx = 21, 37 [Run (AUTO), Run Reverse (AUTO)].
• 2-wire Sequence
When you set A1-03 = 2220 [Initialize Parameters = 2-Wire Initialization] , it will initialize the bypass and set Z2-
01 = 21 [Run FWD]. Run Reverse is not set by default.
2 : Serial Communications
The bypass uses serial communications to enter the Run command.
3 : Option PCB