Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 291
â–  89: Output Current Lim
Setting Value Function Description
89 Output Current Lim The terminal activates when the output current limit is limiting the drive output speed.
â–  94: Loss of Prime
Setting Value Function Description
94 Loss of Prime The terminal activates when the drive is in an LOP [Loss of Prime] condition.
â–  95: Thermostat Fault
Setting Value Function Description
95 Thermostat Fault The terminal activates when the terminal set for H1-xx = 88 [MFDI Function Selection = Thermostat Fault] is active.
â–  96: High Feedback
Setting Value Function Description
96 High Feedback The terminal activates when the drive is in a High Feedback Condition as specified by Y1-11 [High Feedback Level] and Y1-12
[High Feedback Lvl Fault Dly Time] and when the drive detects an HFB [High Feedback Sensed] fault or an HIFB [High Feedback
Sensed] alarm.
â–  97: Low Feedback
Setting Value Function Description
97 Low Feedback The terminal activates when the drive is in a Low Feedback Condition as specified by Y1-08 [Low Feedback Level] and Y1-09 [Low
Feedback Lvl Fault Dly Time] and when the drive detects an LFB [Low Feedback Sensed] fault or an LOFB [High Feedback
Sensed] alarm.
â–  9E: Low PI Auxiliary Control Level
Setting Value Function Description
9E Low PI Auxiliary Control
Level
The terminal activates when the PI Aux Feedback Level is less than YF-09 [PI Aux Control Low Level Detect] or if the drive detects
an LOAUX [Low PI Aux Feedback Level] fault.
â–  9F: High PI Auxiliary Control Level
Setting Value Function Description
9F High PI Auxiliary Control
Level
The terminal activates when the PI Aux Feedback Level is more than YF-12 [PI Aux Control High Level Detect] or if the drive
detects an HIAUX [High PI Aux Feedback Level] fault.
â–  A9: RELAY Operator Control
Setting Value Function Description
A9 RELAY Operator Control
The terminal changes to OFF or ON when you push the RELAY ( ) button. When the terminal is ON, push to turn
it OFF. When the terminal is OFF, push to turn in ON.
â–  AB: Thrust Mode
Setting Value Function Description
AB Thrust Mode The terminal activates when the output frequency is between 0.0 Hz and the value set in Y4-12 [Thrust Frequency] and the Thrust
Bearing function is active.
â–  AC: Setpoint Not Maintained
Setting Value Function Description
AC Setpoint Not Maintained The terminal activates when the drive detects NMS [Setpoint Not Met] condition.

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control