Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 311
â–  H5-22: Speed Search from MODBUS
No.
(Hex.)
Name Description
Default
(Range)
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH). 0
(0, 1)
0 : Disabled
1 : Enabled
If you set H5-22 = 1 and H1-xx = 62 [Speed Search from Fref] at the same time, the drive will detect oPE03 [Multi-
Function Input Setting Err].
â–  H5-23: BACnet Max Master
No.
(Hex.)
Name Description
Default
(Range)
H5-23
(158D)
BACnet Max Master Sets the maximum number of master MAC ID to scan to when the drive polls for the next node (Poll
for Master).
7F
(1 - 7F)
â–  H5-24: BACnet Max Info Frames
No.
(Hex.)
Name Description
Default
(Range)
H5-24
(3DA0)
BACnet Max Info Frames Sets the maximum number of information frames for BACnet. 3
(1 - 255)
â–  H5-25: Function 5A Register 1 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0044H (U1-05)
(0000H - FFFFH)
â–  H5-26: Function 5A Register 2 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0045H (U1-06)
(0000H - FFFFH)
â–  H5-27: Function 5A Register 3 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0042H (U1-03)
(0000H - FFFFH)
â–  H5-28: Function 5A Register 4 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-28
(158C)
RUN
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0049H (U1-10)
(0000H - FFFFH)

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control