5.10 o: Keypad-Related Settings
368 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
o4-09: IGBT Maintenance Setting
No.
(Hex.)
Name Description
Default
(Range)
o4-09
(0525)
IGBT Maintenance Setting Sets the U4-07 [IGBT Maintenance] monitor value. 0%
(0 - 150%)
When you replace a drive, set o4-09 = 0 to reset U4-07. When the o4-09 setting changes, the count of U4-07 starts
again as specified by the setting of o4-09. After you complete the configuration, o4-09 automatically resets to 0.
Note:
The maintenance period changes for different operating environments.
o4-11: Fault Trace/History Init (U2/U3)
No.
(Hex.)
Name Description
Default
(Range)
o4-11
(0510)
Fault Trace/History Init (U2/
U3)
Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History]. 0
(0, 1)
Note:
When you initialize the drive with A1-03 [Initialize Parameters], the drive will not reset the records for U2-xx and U3-xx.
0 : Disabled
Keeps the records of Monitors U2-xx and U3-xx.
1 : Enabled
Resets the records for Monitors U2-xx and U3-xx. After the reset, the drive automatically resets o4-11 to 0.
o4-12: kWh Monitor Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5 Digits]. 0
(0, 1)
Note:
When you initialize the drive with A1-03 [Initialize Parameters], the drive will not reset U4-10 and U4-11.
0 : No Reset
Keeps the monitor values for U4-10 and U4-11.
1 : Reset
Resets the values of U4-10 and U4-11. After the reset, the drive automatically resets o4-12 to 0.
o4-13: RUN Command Counter @ Initialize
No.
(Hex.)
Name Description
Default
(Range)
o4-13
(0528)
RUN Command Counter @
Initialize
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs (Low)], and
U4-25 [Number of Runs (High)].
0
(0, 1)
0 : No Reset
Keeps the monitor values for U4-02, U4-24, and U4-25.
1 : Reset
Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.
o4-22: Time Format
No.
(Hex.)
Name Description
Default
(Range)
o4-22
(154F)
RUN
Time Format Sets the time display format. This parameter is only available on an HOA keypad. 1
(0 - 2)