5.11 S: Special Applications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 387
S3-03: PI2 Control Decimal Place Pos
No.
(Hex.)
Name Description
Default
(Range)
S3-03
(321C)
RUN
PI2 Control Decimal Place
Pos
Sets the decimal place display for secondary PI units. 2
(0 - 3)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
S3-04: PI2 Control Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
S3-04
(321D)
RUN
PI2 Control Unit Selection Sets the units displayed for the PI2 Control parameters and monitor. 48
(0 - 50)
0 : “WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : “Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(S3-18~20)
50 : None
S3-05: PI2 Control Setpoint
No.
(Hex.)
Name Description
Default
(Range)
S3-05
(321E)
RUN
PI2 Control Setpoint Sets the PI2 Control target setpoint. 0.00
(0.00 - 600.00)
Note:
Parameters S3-04 [PI2 Control Unit Selection], S3-03 [PI2 Control Decimal Place Pos], and S3-02 [PI2 Control Transducer Scale] set the
unit, resolution, and upper limit.