5.11 S: Special Applications
400 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : “Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
â– S6-05: EMOVR Independent PID Unit Digit
No.
(Hex.)
Name Description
Default
(Range)
S6-05
(323C)
EMOVR Independent PID
Unit Digit
Sets the number of digits for S6-06 [EMOVR PID Setpoint] when S6-02 = 3[Emergency Override
Ref Selection = Independent PID Mode].
2
(0 - 3)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
â– S6-06: EMOVR PID Setpoint
No.
(Hex.)
Name Description
Default
(Range)
S6-06
(323D)
RUN
EMOVR PID Setpoint Sets the PID Setpoint when S6-02 = 3[Emergency Override Ref Selection = Independent PID Mode]. 0.00
(0 - 600.00)
Note:
When S6-02 = 3: units and resolution are dependent on S6-04 [EMOVR Independent PID Unit] and S6-05 [EMOVR Independent PID Unit
Digit]. Value is internally limited to 300% of S6-03 [EMOVR Independent PID Scale].
â– S6-07: EMOVR Fault Suppression Mode
No.
(Hex.)
Name Description
Default
(Range)
S6-07
(323E)
EMOVR Fault Suppression
Mode
Sets the drive to let Emergency Override disable faults during operation. 0
(0, 1)
0 : Fault Suppression
1 : Test Mode
â– S6-08: EMOVR Drive Enable Input Mode
No.
(Hex.)
Name Description
Default
(Range)
S6-08
(323F)
EMOVR Drive Enable Input
Mode
Sets whether the Drive Enable Input (if programmed) must be inactive (drive is disabled) for
Emergency Override to function.
0
(0, 1)
0 : Drive Enable Status Ignored
1 : EMOVRun Only When Drive Disabled
Note:
You must program Drive Enable to a Digital Input for this parameter to have an effect.