EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
5
5.13 Y: Application Features
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 423
YF-01: PI Aux Control Selection
No.
(Hex.)
Name Description
Default
(Range)
YF-01
(3F50)
PI Aux Control Selection Sets the PI Auxiliary Control function. 0
(0, 1)
0 : Disabled
1 : Enabled
A staged Lead drive will de-stage when U5-16 [PI Aux Ctrl Feedback] is less than YF-04 [PI Aux Control
Minimum Level] for the time set in YF-05 [PI Aux Control Sleep Delay Time].
A staged Lead drive will de-stage when U5-16 is more than YF-24 [PI Auxiliary Ctrl Maximum Level] for the time
set in YF-05.
YF-02: PI Aux Control Transducer Scale
No.
(Hex.)
Name Description
Default
(Range)
YF-02
(3F51)
RUN
PI Aux Control Transducer
Scale
Sets the full scale (10 Vor 20 mA) output of the pressure transducer connected to the analog input
terminal programmed for H3-xx = 27 [PI Aux Control Feedback Level].
145.0
(1.0 - 6000.0)
Note:
Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place Pos] set the unit and resolution.
YF-03: PI Aux Control Setpoint
No.
(Hex.)
Name Description
Default
(Range)
YF-03
(3F52)
RUN
PI Aux Control Setpoint Sets the level to which the drive will try to regulate. 20.0 PSI
(0.0 - 6000.0)
Note:
Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place Pos] set the unit and resolution.
YF-04: PI Aux Control Minimum Level
No.
(Hex.)
Name Description
Default
(Range)
YF-04
(3F53)
RUN
PI Aux Control Minimum
Level
Sets the level below which the drive must be for longer than YF-05 [PI Aux Control Sleep Delay
Time] before the drive goes to sleep and turns off all lag pumps.
10.0 PSI
(0.0 - 6000.0)
Note:
Set this parameter to 0.0 to disable the function.
Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place Pos] set the unit and resolution.
YF-05: PI Aux Control Sleep Delay Time
No.
(Hex.)
Name Description
Default
(Range)
YF-05
(3F54)
RUN
PI Aux Control Sleep Delay
Time
Sets the length of time that the drive will delay before it goes to sleep after the level is less than YF-
04 [PI Aux Control Minimum Level] (when YF-23 = 1 [PI Aux Ctrl Output Level Select = Inverse
Acting]) or more than YF-24 [PI Auxiliary Ctrl Maximum Level] (when YF-23 = 0 [Direct Acting]).
5 s
(0 - 3600 s)
YF-06: PI Aux Control Wake-up Level
No.
(Hex.)
Name Description
Default
(Range)
YF-06
(3F55)
RUN
PI Aux Control Wake-up
Level
Sets the level to wake up the drive when the drive after YF-04 [PI Aux Control Minimum Level] or
YF-24 [PI Auxiliary Ctrl Maximum Level] put the drive to sleep.
30.0 PSI
(-999.9 - +999.9 PSI)

Table of Contents

Other manuals for YASKAWA HV600

Related product manuals