5.14 Z: Bypass Parameters
432 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.100 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
Figure 5.101 Run Delay with Preset Speed Example: Preset Speed
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
2 t1 t
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 0 (Disabled)
Z1-14 Run Delay Frequency Reference = 60.0 Hz
Z1-15 Interlck Wait Time = 10.0 sec
Z1-15 Interlock Wait Time
t3
FAULT : FB02 BAS Ilock Open
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1t2t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 1 (Enable)
Z1-14 Run Delay Frequency Reference = 30.0 Hz
Z1-15 Interlck Wait Time = 0.0 sec (Never Time Out)
Z1-14 Run Delay Frequency Reference
t4