Troubleshooting
6
6.5 Faults
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 495
Code Name Causes Possible Solutions
Uv3 Soft Charge Answerback Fault
The relay or contactor on the soft-charge bypass relay
is damaged.
Re-energize the drive.
If the fault stays, replace the control board or the drive.
Check monitor U4-06 [PreChargeRelayMainte], which shows
the performance life of the soft-charge bypass relay. If U4-06 is
more than 90%, replace the board or the drive. For information
about replacing the board, contact Yaskawa or your nearest sales
representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.
Code Name Causes Possible Solutions
VLTS Thermostat Fault
The digital input from the terminal set for Thermostat
Fault [H1-xx = 88] is active.
Examine the wiring or wait for the motor to cool.
Note:
Do a Fault Reset to clear the fault.
Parameter L5-53 [Thermostat Fault Retry Selection] sets the Auto Restart function of this fault.