EasyManuals Logo

YASKAWA HV600 User Manual

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #604 background imageLoading...
Page #604 background image
9.5 b: Application
604 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-85
(31B3)
RUN
Feedback Loss GoTo
Freq Timeout
When b5-82 = 3 [Feedback Loss 4~20mA Detect Sel = Run At b5-83] and the Feedback
signal is lost, the drive will run at the b5-83 [Feedback Loss Goto Frequency] speed for
this length of time, after which the drive will fault on FDBKL [WIRE Break].
Note:
Set this parameter to 0.0 s to disable the function.
0 s
(0 - 6000 s)
225
b5-86
(31B4)
RUN
Feedback Loss Start
Delay
When you initiate an AUTO Run command, the drive will wait for this length of time
before it will fault on FDBKL [WIRE Break] or use parameter b5-83 [Feedback Loss Goto
Frequency].
0.0 s
(0.0 - 120.0 s)
225
â—† b8: Energy Saving
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b8-01
(01CC)
Energy Saving Control
Selection
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
0
(0, 1)
225
b8-04
(01CF)
Expert
Energy Saving
Coefficient Value
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The
default setting is for Yaskawa motors.
Note:
The minimum values and the maximum values are different for different drive models.
• 2011 to 2024, 4005 to 4008: 0.0 - 2000.0
• 2031 to 2273, 4011 to 4302: 0.00 - 655.00
Determined by E2-11 and
o2-04
(0.00 - 655.00)
226
b8-05
(01D0)
Expert
Power Detection Filter
Time
Sets the time constant to measure output power. 20 ms
(0 - 2000 ms)
226
b8-06
(01D1)
Expert
Search Operation Voltage
Limit
Sets the voltage limit for Search Operation as a percentage of the motor rated voltage. 0%
(0 - 100%)
226

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control

Related product manuals