9.10 H: Terminal Functions
626 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Setting Value Function Description Ref.
16A !Data Logger Error The terminal deactivates when the drive detects LoG [Com Error / Abnormal SD card]. 293
171 !Low PI2 Control
Feedback Level
The terminal deactivates when the PI2 Control Feedback Level is less than S3-13 [PI2 Control Low Feedback Lvl]. 293
172 !High PI2 Control
Feedback Level
The terminal deactivates when the PI2 Control Feedback Level is more than S3-15 [PI2 Control High Feedback Lvl]. 293
189 !Output Current Lim The terminal deactivates when the output current limit is limiting the drive output speed. 293
194 !Loss of Prime The terminal deactivates when the drive is in an LOP [Loss of Prime] condition. 293
195 !Thermostat Fault The terminal deactivates when the terminal set for H1-xx = 88 [MFDI Function Selection = Thermostat Fault] is
active.
293
196 !High Feedback The terminal deactivates when the drive is in a High Feedback Condition as specified by Y1-11 [High Feedback Level]
and Y1-12 [High Feedback Lvl Fault Dly Time] and when the drive detects an HFB [High Feedback Sensed] fault or
an HIFB [High Feedback Sensed] alarm.
293
197 !Low Feedback The terminal deactivates when the drive is in a Low Feedback Condition as specified by Y1-08 [Low Feedback Level]
and Y1-09 [Low Feedback Lvl Fault Dly Time] and when the drive detects an LFB [Low Feedback Sensed] fault or an
LOFB [High Feedback Sensed] alarm.
293
19E !Low PI Auxiliary
Control Level
The terminal deactivates when the PI Aux Feedback Level is less than YF-09 [PI Aux Control Low Level Detect] or if
the drive detects an LOAUX [Low PI Aux Feedback Level] fault.
293
19F !High PI Auxiliary
Control Level
The terminal deactivates when the PI Aux Feedback Level is more than YF-12 [PI Aux Control High Level Detect] or
if the drive detects an HIAUX [High PI Aux Feedback Level] fault.
293
1A9 !RELAY Operator
Control
The terminal changes to OFF or ON when you push the RELAY ( ) button. When the terminal is ON, push
to turn it OFF. When the terminal is OFF, push to turn in ON.
293
1AB !Thrust Mode The terminal deactivates when the output frequency is between 0.0 Hz and the value set in Y4-12 [Thrust Frequency]
and the Thrust Bearing function is active.
293
1AC !Setpoint Not Maintained The terminal deactivates when the drive detects NMS [Setpoint Not Met] condition. 293
1B2 !BAS Interlock The terminal deactivates when the Run command is active or the drive is outputting the voltage. The drive will use this
as an actuation signal for an external damper.
293
1B8 !Pump Fault The terminal deactivates when one of these faults is active: LFB [Low Feedback Sensed], HFB [High Feedback
Sensed], NMS [Setpoint Not Met], or EFx [External Fault (Terminal Sx)].
293
1B9 !Transducer Loss The terminal deactivates when the current into the analog input associated with PID feedback is more than 21 mA or
less than 3 mA, or an FDBKL [WIRE Break] Fault or an FDBKL [Feedback Loss Wire Break] Alarm is active.
293
1BA !PI Auxiliary Control
Active
The terminal deactivates when the PI Auxiliary Controller has an effect on the output speed. 293
1BB !Differential Feedback
Exceeded
The terminal deactivates when the difference between the PID Feedback and the value from the terminal set for H3-xx
= 2D [Differential Feedback] is more than Y4-18 [Differential Level] for the time set in Y4-19 [Differential Lvl
Detection Time].
293
1BC !Sleep Active The terminal deactivates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not deactivate for Sleep Boost function.
293
1BD !Start Delay The terminal deactivates when the Feedback is more than the start level or the Feedback is less than the Inverse PID
and the start timer is timing.
Note:
You must set Y1-04 [Sleep Wake-up Level] ≠ 0 and Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0 to use this
function.
293
1BE !Pre-Charge The terminal deactivates when the drive is in Pre-Charge Mode. 293
1C0 !HAND Mode The terminal deactivates when the drive is in HAND Mode operation. 293
1C1 !AUTO Mode The terminal deactivates when the drive is in AUTO Mode operation. 293
1C2 !OFF Mode The terminal deactivates when the drive is in OFF Mode operation. 293
1C3 !Main Feedback Lost The terminal deactivates when the drive loses the main PID feedback. 293
1C4 !Backup Feedback Lost The terminal deactivates when the drive loses the backup PID feedback. 293