Parameter List
9
9.14 S: Special Applications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 655
No.
(Hex.)
Name Description
Default
(Range)
Ref.
S6-16
(3247)
EMOVR Customer
Safety Mode
Sets the status for the customer safety input (when programmed) that must occur for
Emergency Override to function.
0 : Customer Safety Ignored
1 : EMOVRun Only When Safety OK
2 : EMOVRun Only When Safety NOT OK
Note:
You must set a customer safety to a Digital Input for this parameter to have an effect.
0
(0 - 2)
403
S6-17
(3248)
EMOVR BAS Interlock
Mode
Sets the status for the BAS Interlock input (when programmed) that must occur for
Emergency Override to function.
0 : BAS Interlock Ignored
1 : EMOVRun Only When Interlock OK
2 : EMOVRun When Interlock NOT OK
Note:
Parameter has no effect if BAS Interlock is not programmed to a Digital Input.
0
(0 - 2)
403
S6-20
(324B)
Expert
EMOVR Bypass Fault
ON
Enables bypass-specific faults.
0 : FB02
1 : FB03
2 : FB05
3 : FB06
4 : FB07
5 : FB08
6 : FB09
7 : FB10
8 : FB13
9 : FB15
10 : FB16
11 : FB17
12 : FB18
0
(0 - FFFF)
403
S6-23
(324E)
OV2 Detect Time Sets the detection time of ov2 [DC Bus Overvoltage 2] in 0.1 s increments.
Note:
Set this parameter to 0.0 s to disable ov2 detection.
10.0 s
(0.0 - 1200.0 s)
404

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control

Related product manuals