Parameter List
9
9.18 U: Monitors
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 675
No.
(Hex.)
Name Description MFAO Signal Level
U2-20
(008E)
Heatsink Temp @Fault Shows the heatsink temperature at the fault that occurred most recently.
Use U4-08 [Heatsink Temperature] to monitor the temperature of the heatsink.
Unit: 1 °C
No signal output available
U2-30
(3008)
Fault 1 YYYY Shows the year when the most recent fault occurred. No signal output available
U2-31
(3009)
Fault 1 MMDD Shows the month and day when the most recent fault occurred. No signal output available
U2-32
(300A)
Fault 1 HHMM Shows the time when the most recent fault occurred. No signal output available
U3: Fault History
No.
(Hex.)
Name Description MFAO Signal Level
U3-01
(0090)
1st MostRecent Fault Shows the fault history of the most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-02
(0091)
2nd MostRecent Fault Shows the fault history of the second most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-03
(0092)
3rd MostRecent Fault Shows the fault history of the third most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-04
(0093)
4th MostRecent Fault Shows the fault history of the fourth most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-05
(0804)
5th MostRecent Fault Shows the fault history of the fifth most recent fault. No signal output available
U3-06
(0805)
6th MostRecent Fault Shows the fault history of the sixth most recent fault. No signal output available
U3-07
(0806)
7th MostRecent Fault Shows the fault history of the seventh most recent fault. No signal output available
U3-08
(0807)
8th MostRecent Fault Shows the fault history of the eighth most recent fault. No signal output available
U3-09
(0808)
9th MostRecent Fault Shows the fault history of the ninth most recent fault. No signal output available
U3-10
(0809)
10th MostRecentFault Shows the fault history of the tenth most recent fault. No signal output available
U3-11
(0094)
ElapsedTime@1stFault Shows the cumulative operation time when the most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available
U3-12
(0095)
ElapsedTime@2ndFault Shows the cumulative operation time when the second most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available
U3-13
(0096)
ElapsedTime@3rdFault Shows the cumulative operation time when the third most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available